| Manufacturer part number (MPN) | EASY-E4-DC-8TE1 |
| EAN / GTIN | 4015080892809 |
| Sales unit | pcs |
| Eaton catalogue number | 197219 |
| Depth | 58 mm |
| Height | 90 mm |
| Width | 36 mm |
| Weight | 0.1 kg |
| Drop and topple | 50 mm Drop height, Drop to IEC/EN 60068-2-31 |
| Height of fall (IEC/EN 60068-2-32) - max | 0.3 m |
| Mounting position | Horizontal; Vertical |
| Shock resistance | 15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts |
| Vibration resistance | 57 - 150 Hz, 2 g constant acceleration; According to IEC/EN 60068-2-6; 10 - 57 Hz, 0.15 mm constant amplitude |
| Cable length | 100 m, unscreened, Digital inputs 24 V DC |
| Air pressure | 795 - 1080 hPa (operation) |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 70 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Environmental conditions | Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201 |
| CSA-C22.2 NO. 61010-2-201; Condensation | prevent with appropriate measures |
| Relative humidity | 5 - 95 % (IEC 60068-2-30, IEC 60068-2-78) |
| Connection type | Screw terminal |
| Static heat dissipation, non-current-dependent Pvs | 1 W |
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) | 0.5 A |
| Heat dissipation | 3.4 W (at 24 V DC) |
| Inrush current | 12.5 A (for 6 ms) |
| Power consumption | 1 W |
| Rated operational current (Ie) | Max. 0.5 A at signal „1” DC per channel |
| Rated operational voltage | 20.4 - 28.8 V DC; 20.4 - 28.8 V DC (Transistor outputs); 24 V DC (-15 %/+ 20 % - power supply); 24 V DC (transistor outputs); 24 V DC (digital inputs) |
| Supply current | 18/32 mA, Normally⁄max., On 0 signal, Transistor outputs; 24/44 mA, Normally⁄max., On 1 signal, Transistor outputs |
| Supply voltage at DC - max | 28.8 VDC |
| Supply voltage at DC - min | 20.4 VDC |
| Air discharge | 8 kV |
| Burst impulse | 2 kV, Signal cable; 2 kV, Supply cable; According to IEC/EN 61000-4-4 |
| Contact discharge | 6 kV |
| Electromagnetic fields | 10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3); 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3); 1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3) |
| Immunity to line-conducted interference | 10 V (according to IEC/EN 61000-4-6) |
| Radio interference class | Class B (EN 61000-6-3) |
| Surge rating | 1 kV, Supply cables, asymmetrical, power pulses (Surge), EMC; 0.5 kV, Supply cables, symmetrical, power pulses (Surge), EMC; According to IEC/EN 61000-4-5, power pulses (Surge), EMC |
| Voltage dips | 20 ms; ≤ 10 ms, Bridging voltage dips |
| Features | Expandable; Expansion device; Parallel connection of transistor outputs with resistive load, inductive load with external suppressor circuit, combination within a group - Group 1: Q1 to Q4 |
| Functions | Thermal cutout |
| Indication | LCD-display base unit used as Output status indication of Transistor outputs; LCD-display base unit used as status indication of Digital inputs 24 V DC |
| Degree of protection | IP20 |
| Insulation resistance | According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 |
| Mounting method | Rail mounting possible; Top-hat rail fixing (according to IEC/EN 60715, 35 mm); Wall mounting/direct mounting; Screw fixing using fixing brackets ZB4-101-GF1 (accessories); Front build in possible |
| Operating frequency | Dependent on the cycle- and transmission-time of the expansion devices; Depending on the suppressor circuit (Inductive load to EN 60947-5-1, with external suppressor circuit, Max. switching frequency, max. duty factor); Dependent on the cycle time of the basic device |
| Overvoltage category | III |
| Pollution degree | 2 |
| Product category | Control relays easyE4 |
| Protocol | MODBUS; TCP/IP |
| Residual current | 0.1 mA (on signal "1" per channel) |
| Residual ripple | ≤ 5 %; 5 % (transistor outputs) |
| Software | EASYSOFT-SWLIC/easySoft |
| Type | easyE4 extension |
| Voltage type | DC |
| Input current | 40 mA |
| Input voltage | Signal 0: ≤ 5 V DC (I1 - I4, Digital inputs |
| 24 V DC); Signal 1 | ≥ 15 V DC (I1 - I4, Digital inputs, 24 V DC) |
| Lamp load | Max. 3 W (without Rv per channel) |
| Number of inputs (analog) | 0 |
| Number of inputs (digital) | 4 |
| Number of outputs (analog) | 0 |
| Number of outputs (digital) | 4 |
| Output | 2 A, Max. total current, Outputs; 4 Transistor Outputs; Parallel connection of max. 4 Transistor outputs; Voltage; Current |
| Output voltage | U = Uₑ - 1 V (signal 1 at Iₑ = 0.5 A, transistor outputs); Max. 2.5 V (at status 0 per channel, transistor outputs) |
| Explosion safety category for dust | None |
| Explosion safety category for gas | None |
| Protection against polarity reversal | Yes, for supply voltage (Siemens MPI optional); For transistor outputs (Caution: A short circuit will result if 0 V/earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles) |
| Short-circuit current | 6.8 A, Transistor outputs |
| Short-circuit protection | Yes, electronic (Q1 - Q4), Transistor outputs; ≥ 1A (T), Fuse, Power supply |
| Short-circuit tripping current | 0.7 ≤ Ie ≤ 1.7 per output, For Ra ≤ 10 mΩ, Depending on number of active channels and their load, Transistor outputs |
| Screwdriver size | 3.5 x 0.8 mm, Terminal screw |
| Terminal capacity | 0.2 - 4 mm² (AWG 22 - 12), solid; 0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule |
| Tightening torque | 0.6 Nm, Screw terminals |
| Document Name | Description Action |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | Yes |
| Certified for UL hazardous location group A (acetylene) | Yes |
| Certified for UL hazardous location group B (hydrogen) | Yes |
| Certified for UL hazardous location group C (ethylene) | Yes |
| Certified for UL hazardous location group D (propane) | Yes |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | Yes |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 20.4–28.8 V |
| Switching current | 0.5 A |
| Number of digital inputs | 4 |
| Number of digital outputs | 4 |
| With relay output | No |
| With optical interface | No |
| Supporting protocol for TCP/IP | Yes |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | Yes |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| Redundancy | No |
| With display | No |
| Basic device | No |
| Expandable | Yes |
| Expansion device | Yes |
| With time switch clock | No |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | Yes |
| Front built-in possible | Yes |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Country of origin | Estonia |