| Manufacturer part number (MPN) | E10 |
| EAN / GTIN | 4015080903512 |
| Sales unit | pcs |
| Package quantity | 50 pcs |
| Eaton catalogue number | 090351 |
| Depth | 6 mm |
| Height | 29 mm |
| Width | 18 mm |
| Weight | 0.003 kg |
| Certifications | CE; UL Category Control No.: NKCR; UL; CSA-C22.2 No. 14-05; IEC/EN 60947; UL 508; UL File No.: E29184; CSA; CSA Class No.: 3211-03; CSA File No.: 46552; IEC/EN 60947-5 |
| Electric connection type | Screw connection |
| Operating frequency | 3600 Operations/h |
| Pollution degree | 3 |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Actuating force - max | 3 N |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Heat dissipation per pole, current-dependent Pvid | 0.1 W |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 0 |
| Number of contacts (normally open contacts) | 1 |
| Number of switches (fault signal) | 0 |
| Connection to SmartWire-DT | No |
| Rated impulse withstand voltage (Uimp) | 4000 V AC |
| Terminal capacity | 0.5 - 1.0 mm² |
| Mounting position | As required |
| Terminal size | 2.8 x 0.8 mm to DIN 46247 and IEC 60760, Fast-on connectors; 2.8 x 0.8 mm to DIN 46244, Blade terminal |
| Rated conditional short-circuit current (Iq) | 1 kA |
| Connection type | Blade terminal |
| Mounting method | Front fastening |
| Overvoltage category | III |
| Control circuit reliability | 1 failure per 10,000,000 switching operations (Statistically determined, at 24 V DC/5 mA); 1 failure per 5,000,000 switching operations (statistically determined, at 5 V DC/1 mA) |
| Degree of protection | IP20, with Insulated ferrule ISH2,8 |
| Model | Top mounting |
| Lamp holder | None |
| Rated operational current (Ie) | 4 A at AC-15, 110 V; 4 A at AC-15, 48 V |
| Lifespan, mechanical | 100,000,000 Operations |
| Short-circuit protection | FAZ-B6/1, Fuseless |
| Product category | Accessories |
| Short-circuit protection rating | Max. 10 A gG/gL, Fuse, Contacts |
| Rated insulation voltage (Ui) | 250 V |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 6 A |
| Rated operational current (Ie) at AC-15, 24 V | 4 A |
| Rated operational current (Ie) at DC-13, 110 V | 0.5 A |
| Rated operational current (Ie) at DC-13, 220 V, 230 V | 0.2 A |
| Rated operational current (Ie) at DC-13, 24 V | 1.5 A |
| Rated operational current (Ie) at DC-13, 42 V | 1 A |
| Rated operational current (Ie) at DC-13, 60 V | 0.8 A |
| Rated operational current for specified heat dissipation (In) | 4 A |
| Rated operational voltage (Ue) at AC - max | 250 V |
| Shock resistance | 40 g, Mechanical, According to IEC/EN 60068-2-27, Sinusoidal shock 11 ms; Mechanical, According to IEC/EN 60068-2-27 |
| Country of origin | China |