Contact element 1S FRONT (M22-K10)

Eaton · Control & Automation · Pushbuttons & Pilot Lights · Ireland · eaton.com
Part Number
M22-K10  ·  HS 8538.90
Contact element 1S FRONT (M22-K10)

Eaton M22-K10 Contact Element 1S Front.

Technical Specifications

Manufacturer part number (MPN)M22-K10
EAN / GTIN4015082163761
Sales unitpcs
Package quantity20 pcs
Eaton catalogue number216376
Depth38 mm
Height10 mm
Width32 mm
Weight0.01 kg
CompliancesCE Marked
CertificationsCSA Std. C22.2 No. 94-91; UL 508; IEC 60947-5; CSA Std. C22.2 No. 14-05; EN 60947-5; VDE; CSA File No.: 012528; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CSA; UL Category Control No.: NKCR; UL File No.: E29184; UL/CSA; CE; IEC/EN 60947-5; IEC; IEC 60947-5-1; CSA Class No.: 3211-03; UL
Actuating force - max5 N
Ambient operating temperature - max70 °C
Ambient storage temperature - max85 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Connection to SmartWire-DTNo
Control circuit reliability1 failure per 10,000,000 switching operations (Statistically determined, at 24 V DC/5 mA); 1 failure per 5,000,000 switching operations (statistically determined, at 5 V DC/1 mA)
Number of contacts (change-over contacts)0
Number of contacts (normally closed contacts)0
Number of contacts (normally open contacts)1
Heat dissipation per pole, current-dependent Pvid0.11 W
Rated operational current for specified heat dissipation (In)6 A
Conventional thermal current Ith of auxiliary contacts (1-pole, open)4 A
Rated insulation voltage (Ui)500 V
Rated operational current (Ie)1 A - 250 V DC; 5 A – 600 V AC
Rated operational current (Ie) at AC-15, 115 V6 A
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V6 A
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V4 A
Rated operational current (Ie) at AC-15, 500 V2 A
Rated operational current (Ie) at DC-13, 110 V0.6 A
Rated operational current (Ie) at DC-13, 220 V, 230 V0.3 A
Rated operational current (Ie) at DC-13, 24 V3 A
Rated operational current (Ie) at DC-13, 42 V1.7 A
Rated operational current (Ie) at DC-13, 500 V0.1 A
Rated operational current (Ie) at DC-13, 60 V1.2 A
Rated operational voltage (Ue) at AC - max500 V
Rated operational voltage (Ue) at DC - max220 V
Electric connection typeScrew connection
Degree of protectionIP20
Lifespan, electrical1,000,000 Operations (at 230 V, AC-15, 1 A); 700,000 Operations (at 230 V, AC-15, 3 A); 1,200,000 Operations (at 12 V, DC-13, 2.8 A); 1,600,000 Operations (at 230 V, 0.5 A)
Lifespan, mechanical5,000,000 Operations
ModelTop mounting and integrable
Operating frequency3600 Operations/h
Operating torque0.8 Nm
Overvoltage categoryIII
Pollution degree3
Product categoryAccessories
Rated impulse withstand voltage (Uimp)6000 V AC
TypeAuxiliary contact
Connection typeFront fixing; Single contact
Mounting methodFront fastening
Short-circuit protectionPKZM0-10/FAZ-B6/1, Contacts, Max. short-circuit protective device, Fuseless
Short-circuit protection ratingMax. 10 A gG/gL, Fuse, Auxiliary contacts; Max. 10 A gG/gL, Fuse, Contacts
Terminal capacity (flexible with ferrule)0.5 - 1.5 mm²
Terminal capacity (solid)0.75 - 2.5 mm²
Terminal capacity (solid/flexible with ferrule)1 x (0,75 - 2,5) mm²; 2 x (0,75 - 2,5) mm²
Terminal capacity (stranded)0.5 - 2.5 mm²
Country of originGermany