| Manufacturer part number (MPN) | DCM-63/4-SK+HC |
| EAN / GTIN | 8711426313996 |
| Sales unit | pcs |
| Eaton catalogue number | 1314015 |
| Depth | 146 mm |
| Height | 74 mm |
| Width | 84 mm |
| Weight | 0.46 kg |
| Certifications | IEC/EN 60947; RoHS; IEC/EN 60204; IEC/EN 60947-3; KEMA; VDE 0660; CE; Lloyds; EAC |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient storage temperature - min | -30 °C |
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Heat dissipation per pole, current-dependent Pvid | 3.9 W |
| Rated operational current for specified heat dissipation (In) | 63 A |
| Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3) | 504 A |
| Rated insulation voltage (Ui) | 690 V |
| Rated operational current (Ie) at AC-21, 400 V, 415 V | 63 A |
| Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V | 63 A |
| Rated operational current (Ie) at AC-23A, 400 V, 415 V | 63 A |
| Rated operational power at AC-23A, 400 V, 50 Hz | 63 kW |
| Rated operational voltage (Ue) at AC - max | 415 V |
| Rated uninterrupted current (Iu) | 63 A |
| Uninterrupted current | Rated uninterrupted current Iu is specified for max. cross-section. |
| Features | Version as main switch; Version as maintenance-/service switch |
| Functions | Optional Stop Function |
| Number of poles | Four-pole |
| Actuator color | Other |
| Actuator type | Other |
| Connection type | Horizontal |
| Degree of protection | NEMA Other |
| Degree of protection (front side) | IP20 |
| Lifespan, mechanical | 10,000 Operations |
| Mounting method | Surface mounting |
| Mounting position | As required |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product Category | Main switch Switch-disconnector |
| Rated impulse withstand voltage (Uimp) | 6000 V |
| Safety parameter (EN ISO 13849-1) | B10d values as per EN ISO 13849-1, table C.1 |
| Suitable for | Ground mounting; Distribution board installation |
| Breaking current | 7 kA |
| Light-through energy | Max. 12 kA²s |
| Rated conditional short-circuit current (Iq) | 50 kA |
| Rated short-circuit making capacity (Icm) | 1.4 kAeff |
| Rated short-time withstand current (Icw) | 1,5 kA, Contacts, 1 second; 1.5 kA |
| Short-circuit protection rating | 50, Fuse, Contacts |
| Stripping length (main cable) | 14 mm |
| Terminal capacity | 2.5 - 16 mm², solid; 1.5 - 25 mm², flexible |
| Country of origin | United Kingdom |