cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety Relay ESR5-NV3-30

Eaton · Safety & Detection · Safety Relays · Ireland · eaton.com
Part Number
ESR5-NV3-30  ·  HS 8536.49
Safety Relay ESR5-NV3-30

Eaton ESR5-NV3-30 Safety Relay emergency stop, 24 V DC, 4 veier(2del.).

Technical Specifications

Manufacturer part number (MPN)ESR5-NV3-30
EAN / GTIN4015081168453
Sales unitpcs
Eaton catalogue number118705
Depth114.5 mm
Height99 mm
Width22.5 mm
Weight0.171 kg
Mounting positionAs required
Prooftest240 Months (High Demand)
Switching capacity3 A at 3600 O/h, DC-13 at 24 V, Outputs; 5 A at 3600 O/h, AC-15 at 230 V, Outputs; 0.4 W; In accordance with IEC 60947-5-1, Outputs
Vibration resistance10 - 150 Hz
Amplitude0.15 mm
Acceleration2 g, (IEC/EN 60068-2-6)
Air pressure795 - 1080 hPa (operation)
AltitudeMax. 2000 m
Ambient operating temperature - max45 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-20 °C
Ambient storage temperature - min-40 °C
Climatic proofingDry heat to IEC 60068-2-2; Damp heat, constant, to IEC 60068-2-3; Cold to EN 60068-2-1
Environmental conditionsClearance in air and creepage distances according to EN 60947-1, UL 508, CSA C22.2
No. 14-95; CondensationNon-condensing
Operating temperature - max45 °C
Operating temperature - min-20 °C
Relative humidity< 75 %
Static heat dissipation, non-current-dependent Pvs7.8 W
Inrush current0.025 - 6 A
Power supply circuit1.8 W (DC operated)
Rated control supply voltage (Us) at AC
50 Hz - max26.4 V
Rated control supply voltage (Us) at AC
Rated control supply voltage (Us) at AC
60 Hz - max26.4 V
Rated control supply voltage (Us) at AC
60 Hz - min20.4 V
Rated control supply voltage (Us) at DC - max24 V
Rated insulation voltage (Ui)250 V
Rated operational voltage24 V DC (power supply); Approx. 24 V DC at input, starting and feedback circuit; 230 V AC
Short-circuit current0.1 A, Input data
Short-circuit protectionFuse 10 A gL/gG NEOZED, For output circuits, External
Short-circuit protection rating10A gL/gG, NEOZED (N/O), Output fuse, External, Output data; 6A gL/gG, NEOZED (N/C), Output fuse, External, Output data
Electric connection typeScrew connection
FeaturesAutomatic start; Manual start; Basic insulation; 2 Non-delayed enable current paths
Fitted withApproval for TÜV; Start input; Selectable cross-circuit detection; Detachable clamps; Feedback circuit; Approval according to UL
Functions1-channel; 2-channel; Time function
MaterialContacts: silver tin oxide, gold plated (AgSnO2
0.2 µm Au); EnclosurePolyamide (PA), not reinforced
Connection typeM3 screw terminals
Current consumption75 mA, DC
Degree of protectionTerminals: IP20; IP20; Installation location: ≥ IP54; Enclosure: IP20
Duty factor100 %
Emitted interferenceAccording to EN 61000-6-4
Interference immunityAccording to EN-61000-6-2; According to EN 662061_x
LED indicatorStatus indication of SmartWire-DT network: Green LED
Lifespan, mechanical10,000,000 Operations
Lifetime240 month
ModelBasic device
Mounting methodTop-hat rail fixing (according to IEC/EN 60715, 35 mm); Rail mounting possible
Mounting width22.5 mm
Overvoltage categoryIII
Pollution degree2
Power lossNormally 7.8 W
Product categoryElectronic safety relays
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)4000 V AC
Recovery time330 ms (restart)
Safety parameter (EN ISO 13849-1)400,000 switching cycles, B10d; Cat. 4, Category; PL e, Performance level
Safety parameter (IEC 62061)SIL 3 only for high demand requirements, Safety integrity level; Cat. 4, Category; 18 x 10-10, PFHd, Probability of failure per hour; SIL 3, Safety integrity level; SILCL 3, Safety integrity level claim limit; SIL 3, Safety integrity level, In accordance with IEC 61508
Stop category (IEC 60204)0; 1
Switching frequencyMax. 0.5 Hz, Input data
TypeEmergency stop category 1; emergency switching off Feedback circuit Light curtain Protective door
Voltage typeDC
Input∞ ms, Simultaneity for inputs 1/2
Nominal current3.5 A
Number of inputsOne- and two-channel
Number of outputs (safety related, delayed) with contact2
Number of outputs (safety related, undelayed) with contact2
Number of outputs (signaling function, delayed) with contact0
Number of outputs (signaling function, undelayed) with contact0
Off-delay0.1 - 30 s (± 40 %, K3, K4 adjustable)
Permissible total cable resistance500 Ω (input and starting circuits for UN)
Pick-up time150 ms typ. (at Uₑ in automatic mode); 150 ms typ. (controlled start, K1, K2 - for UN manual operation); 150 ms typ. (controlled start, K1, K2 - for UN automatic mode); 150 ms typ. (at Uₑ in manual mode)
Quadratic summation current55 A² (ITH² = I1² + I2² + I3² + I4² + I5²)
Reset timeNormally 100 ms (delayed contacts); 20 ms (non-delayed contacts)
Resistance500 Ω (impedance)
Switching voltage250 V
Uninterrupted current6 A N/O, Limiting continuous current; 6 A N/C, Limiting continuous current
Screwdriver size3.5 x 0.6 mm, Terminal screw; 2, Terminal screw, Pozidriv screwdriver
Stripping length (main cable)7 mm
Terminal capacity2 x (0.2 – 1) mm², solid; 24 - 12 AWG, solid or stranded; 1 x (0.2 – 2.5) mm², solid; 2 x (0.25 – 1) mm², flexible with ferrule; 1 x (0.25 – 2.5) mm², flexible with ferrule
Tightening torque0.6 Nm, Screw terminals
Operating voltage DC24 V
Power consumption7.8 W
Supply voltage DC24 V
Rated switch current5 A
Control voltage 124 V
Control voltage 224 V
Type of control voltage 1DC
Type of control voltage 2DC
Suitable for monitoring of position switchesYes
Suitable for monitoring of emergency-stop circuitsYes
Suitable for monitoring of valvesNo
Suitable for monitoring of tactile sensorsNo
Suitable for monitoring of magnetic switchesNo
Suitable for monitoring of proximity switchesNo
Type of electric connectionScrew connection
Suitable for rail mountingYes
Rated control supply voltage AC 50 Hz0–26.4 V
Voltage type for actuatingDC
With detachable clampsYes
Evaluation inputsOne- and two-channel
With start inputYes
With muting functionNo
With feedback circuitYes
Release-delay0.1–30 s
Number of outputs, safety related, undelayed, with contact2
Number of outputs, safety related, delayed, with contact2
Type of safety according to IEC 61496-1None
Stop category according to IEC 602041
Performance level according to EN ISO 13849-1Level e
SIL according to IEC 615083
With approval for BG BIANo
With approval according to ULYes
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents