cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety Relay ESR5-NO-31-230VAC

Eaton · Safety & Detection · Safety Relays · Ireland · eaton.com
Part Number
ESR5-NO-31-230VAC  ·  HS 8536.49
Safety Relay ESR5-NO-31-230VAC

Eaton ESR5-NO-31-230VAC Control voltage 230VAC 50,60 Hz.

Technical Specifications

Manufacturer part number (MPN)ESR5-NO-31-230VAC
EAN / GTIN4015081175062
Sales unitpcs
Eaton catalogue number119380
Depth114.5 mm
Height99 mm
Width22.5 mm
Weight0.181 kg
Mounting positionAs required
Prooftest240 Months (High Demand); 78 Months (Low Demand)
Switching capacityIn accordance with IEC 60947-5-1, Outputs; 0.1 W; 5 A at 360 O/h, AC-15 at 230 V, Outputs; 5 A at 360 O/h, DC-13 at 24 V, Outputs
Vibration resistance10 - 150 Hz
Amplitude0.15 mm
Acceleration2 g, (IEC/EN 60068-2-6)
Air pressure795 - 1080 hPa (operation)
AltitudeMax. 2000 m
Ambient operating temperature - max55 °C
Ambient storage temperature - max85 °C
Ambient operating temperature - min-20 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-3; Dry heat to IEC 60068-2-2
Environmental conditionsClearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2
No. 14-95; CondensationNon-condensing
Operating temperature - max55 °C
Operating temperature - min-20 °C
Relative humidity< 75 %
Static heat dissipation, non-current-dependent Pvs5.43 W
Inrush current0.1 - 6 A
Power supply circuit2.9 W (DC operated); 5.8 W (AC operated 50/60 Hz)
Rated control supply voltage (Us) at AC
50 Hz - max26.4 V
Rated control supply voltage (Us) at AC
Rated control supply voltage (Us) at AC
60 Hz - max230 V
Rated control supply voltage (Us) at AC
60 Hz - min20.4 V
Rated insulation voltage (Ui)250 V
Rated operational voltage230 V AC (power supply); 230 V AC; Approx. 24 V DC at input, starting and feedback circuit
Short-circuit current0.7 A, Input data
Short-circuit protectionFuse 4 A gL/gG (Signal current paths), For output circuits, External; Fuse 10 A gL/gG (Enable current paths), For output circuits, External; Short-circuit proof, 115 V/230 V, Fuse for control circuit supply, Control circuit
Short-circuit protection rating10A gL/gG, NEOZED (N/O), Output fuse, External, Output data; 6A gL/gG, NEOZED (N/C), Output fuse, External, Output data
Electric connection typeScrew connection
Features3 Non-delayed enable current paths; Reinforced insulation; Safe insulation; Automatically/manually monitored start; 6 kV between A1-A2 / logic / enable and signal current paths; Basic insulation
Fitted withFeedback circuit; Approval according to UL; Approval for TÜV; Start input; Detachable clamps
Functions1-channel; 2-channel
MaterialEnclosure: Polyamide (PA), not reinforced; Contacts: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au)
Connection typeM3 screw terminals
Current consumption22 mA, AC
Degree of protectionInstallation location: ≥ IP54; Enclosure: IP20; Terminals: IP20; IP20
Duty factor100 %
Emitted interferenceAccording to EN 61000-6-4
Interference immunityAccording to EN 61000-6-2
LED indicatorStatus indication of SmartWire-DT network: Green LED
Lifespan, mechanical10,000,000 Operations
ModelBasic device
Mounting methodTop-hat rail fixing (according to IEC/EN 60715, 35 mm); Rail mounting possible
Mounting width22.5 mm
Overvoltage categoryIII
Pollution degree2
Power lossNormally 5.43 W
Product categoryElectronic safety relays
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)4000 V AC
Recovery time1000 ms
Safety parameter (EN ISO 13849-1)PL e, Performance level; 230,000 switching cycles, B10d; Cat. 4, Category
Safety parameter (IEC 62061)SILCL 3, Safety integrity level claim limit; SIL 3, Safety integrity level; Cat. 4, Category; SIL 3, Safety integrity level, In accordance with IEC 61508; 1.89 x 10-10, PFHd, Probability of failure per hour
Stop category (IEC 60204)0
Suitable forModule used to safely interrupt electrical circuits; Monitoring of position switches; Safety relay for monitoring emergency stop and protective door switch; Monitoring of emergency-stop circuits
Switching frequencyMax. 0.5 Hz, Input data
TypeEmergency stop category 0; emergency switching off Feedback circuit Protective door
Voltage typeAC
Input∞ ms, Simultaneity for inputs 1/2
Nominal current35 A
Number of inputsOne- and two-channel
Number of outputs (safety related, delayed) with contact0
Number of outputs (safety related, undelayed) with contact3
Number of outputs (signaling function, delayed) with contact0
Number of outputs (signaling function, undelayed) with contact1
Permissible total cable resistance50 Ω (input and starting circuits for UN)
Pick-up time40 ms typ. (at Uₑ in manual mode); 300 ms typ. (at Uₑ in automatic mode); 40 ms typ. (K1, K2 - for UN manual operation); 300 ms typ. (K1, K2 - for UN automatic mode); 330 ms typ. (if actuated via A1)
Quadratic summation current72 A² (ITH² = I1² + I2² + I3²)
Reset time20 ms (two-channel); Normally 150 ms (single-channel)
Resistance11 Ω (impedance)
Switching voltage250 V
Uninterrupted current6 A N/O, Limiting continuous current; 5 A N/C, Limiting continuous current
Screwdriver size2, Terminal screw, Pozidriv screwdriver; 3.5 x 0.6 mm, Terminal screw
Stripping length (main cable)7 mm
Terminal capacity1 x (0.25 – 2.5) mm², flexible with ferrule; 2 x (0.25 – 1) mm², flexible with ferrule; 24 - 12 AWG, solid or stranded; 1 x (0.2 – 2.5) mm², solid; 2 x (0.2 – 1) mm², solid
Tightening torque0.6 Nm, Screw terminals
Operating voltage AC 50 Hz230 V
Operating voltage AC 60 Hz230 V
Power consumption5.43 W
Supply voltage AC 50 Hz230 V
Supply voltage AC 60 Hz230 V
Rated switch current4 A
Control voltage 1230 V
Control voltage 2230 V
Type of control voltage 1AC
Type of control voltage 2AC
Suitable for monitoring of position switchesYes
Suitable for monitoring of emergency-stop circuitsYes
Suitable for monitoring of valvesNo
Suitable for monitoring of tactile sensorsNo
Suitable for monitoring of magnetic switchesNo
Suitable for monitoring of proximity switchesNo
Type of electric connectionScrew connection
Suitable for rail mountingYes
Rated control supply voltage AC 50 Hz0–26.4 V
Voltage type for actuatingAC
With detachable clampsYes
Evaluation inputsOne- and two-channel
With start inputYes
With muting functionNo
With feedback circuitYes
Number of outputs, safety related, undelayed, with contact3
Type of safety according to IEC 61496-1None
Stop category according to IEC 602040
Performance level according to EN ISO 13849-1Level e
SIL according to IEC 615083
With approval for BG BIANo
With approval according to ULYes
Country of originGermany