cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Voltage monitoring relay (EMR6-VM600-A-1)

Eaton · Control & Automation · Monitoring Relays · Ireland · eaton.com
Part Number
EMR6-VM600-A-1  ·  HS 8536.49
Voltage monitoring relay (EMR6-VM600-A-1)

Technical Specifications

Manufacturer part number (MPN)EMR6-VM600-A-1
EAN / GTIN4015081788200
Sales unitpcs
Eaton catalogue number184784
Depth103.7 mm
Height85.6 mm
Width22.5 mm
Weight0.154 kg
CertificationsUL508; EAC; RMRS; CCC; RCM; CSA-C22.2 No. 14; GL
Ambient operating temperature - max60 °C
Ambient storage temperature - max85 °C
Ambient operating temperature - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30
Air dischargeAir/contact discharge, according to IEC/EN 61000-4-2, level 3
Burst impulseAccording to IEC/EN 61000-4-4, level 3
Electromagnetic compatibilityAccording to IEC/EN 60947-6-2
Immunity to line-conducted interferenceLevel 3 (according to IEC/EN 61000-4-6)
Immunity to radiationLevel 3 (according to IEC/EN 61000-4-3)
Surge ratingAccording to IEC/EN 61000-4-5 Level 4
Electric connection typeScrew connection
FunctionsSingle-phase under voltage possible; DC-under voltage; Single-phase over voltage possible; DC-over voltage
Monitoring functionUndervoltage; Overvoltage
Voltage measurement - max600 V
Voltage measurement - min3 V
Degree of protectionEnclosure: IP50; Terminals: IP20
LED indicatorStatus indication of energized output relay: Yellow LED; Status indication of Supply voltage: Yellow LED; Status indication of errors: Red LED; Other states depending on fault (see IL): Measured value; Status indication of Supply voltage: Green, solid light
Lifespan, mechanical30,000,000 Operations
Mounting positionAs required
Overvoltage categoryIII
Pollution degree3
Product CategoryEMR Measuring and monitoring relays
Rated impulse withstand voltage (Uimp)4000 V AC
Shock resistanceClass 2
TypeVoltage monitor
Voltage typeAC/DC
Hysteresis3 - 30 %
Threshold value3 V AC, Min. undervoltage response value; 3 V AC, Min. overvoltage response value; 600 V AC, Max. undervoltage response value; 600 V AC, Max. overvoltage response value
Duty factor100 %, Power supply
Power consumption2.6 VA
Rated control supply voltage (Us) at AC, 50 Hz - max240 V
Rated control supply voltage (Us) at AC, 50 Hz - min24 V
Rated control supply voltage (Us) at AC, 60 Hz - max240 V
Rated control supply voltage (Us) at AC, 60 Hz - min24 V
Rated control supply voltage (Us) at DC - max240 V
Rated control supply voltage (Us) at DC - min24 V
Rated frequency - max60 Hz
Rated frequency - min50 Hz
Supply voltage24 - 240 V AC, 50/60 Hz; 24 - 240 V DC
Voltage tolerance0.85 x Uc; 1.1 x Uc
Lifespan, electrical100,000 Operation (at 230 V, AC-12, 4 A)
Number of contacts (change-over contacts)2
Number of contacts (normally closed contacts)0
Number of contacts (normally open contacts)0
Connection typeSnap fixing, top-hat rail IEC/EN 60715
Screwdriver size5.5 x 0.8 mm, Terminal screw
Terminal capacity (flexible with ferrule AWG)2 x 18-16
Terminal capacity (flexible with ferrule)2 x 0.5-1.5 mm²
Terminal capacity (solid AWG)18 - 14
Terminal capacity (solid)1 x 0.5-2.5 mm²
Tightening torqueMin. 0.5 Nm, Screw terminals; 0.8 Nm, Screw terminals
Delay timeAdjustable from 0.1 - 30 s, Response delay time
Timing cycleAdjustable from 0.1 – 30 s, Reset delay/Off-delay time
Operating voltage AC 50 Hz24–240 V
Operating voltage AC 60 Hz24–240 V
Operating voltage DC24–240 V
External power supply requiredNo
Supply voltage AC 50 Hz24–240 V
Supply voltage AC 60 Hz24–240 V
Supply voltage DC24–240 V
Rated switch current4 A
Type of electric connectionScrew connection
With detachable clampsNo
Single-phase under voltage possibleYes
Three-phase under voltage possibleNo
Single-phase overvoltage possibleYes
Three-phase overvoltage possibleNo
Single-phase hysteresis possibleNo
Three-phase hysteresis possibleNo
Contains function DC-under voltageYes
Contains function DC overvoltageYes
Contains function DC-voltage hysteresisNo
Voltage measuring range 13–600 V
Type of voltage measuring rangeAC/DC
Rated control supply voltage AC 50 Hz24–240 V
Rated control supply voltage AC 60 Hz24–240 V
Rated control supply voltage DC24–240 V
Voltage type for actuatingAC/DC
Response value voltage3–600 V
Min. adjustable delay-on energization time0.1 s
Max. permitted delay-on energization time30 s
Number of contacts as change-over contact2
Country of originGermany
Min. adjustable off-delay time0 s

Properties

MOQ1

Cross-References

Attached Documents