cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Direktestarter EMS2-DOS-T-9-SWD

Eaton · Drives & Controllers · Motor Starters · Ireland · eaton.com
Part Number
EMS2-DOS-T-9-SWD  ·  HS 8536.50
Direktestarter EMS2-DOS-T-9-SWD

Eaton EMS2-DOS-T-9-SWD Direktestarter, 24 V DC, 1,5 - 7 (AC-53a), 9 (AC-51) A, Push-In Terminals, SmartWire-DT slave.

Technical Specifications

Manufacturer part number (MPN)EMS2-DOS-T-9-SWD
EAN / GTIN4015081930869
Sales unitpcs
Eaton catalogue number192389
Depth114.5 mm
Height99 mm
Width22.5 mm
Weight0.297 kg
CertificationsUL508; IEC 61508; EN ISO 13849; IEC/EN 60947-4-2; UL File No.: E338590; UL Category Control No.: NLDX, NLDX7; PTB 19 ATEX 3000; UL 60947-4-1; CSA-C22.2 No. 60947-4-1-14; CE marking; UL listed; Certified by UL for use in Canada; UL report applies to both US and Canada
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-5 °C
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid12 W
Heat dissipation detailsIf necessary, Allow for derating
Rated operational current for specified heat dissipation (In)9 A
Static heat dissipation, non-current-dependent Pvs2 W
Inrush current120 mA (draw)
Rated actuating current (Ic)5 mA
Rated control supply current Is60 mA
Rated control supply voltage19.2 - 30 V DC
Rated control supply voltage (Us) at DC - max24 V
Rated control supply voltage (Us) at DC - min24 V
Rated control voltage (Uc)24 V (Actuating circuit ON, L, R)
Rated operational current (Ie)9 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V7 A
Rated operational current (Ie) at AC-519 A
Rated operational current (Ie) at AC-53A - max7 A
Rated operational power at AC-3, 220/230 V, 50 Hz1.5 kW
Rated operational power at AC-3, 380/400 V, 50 Hz3 kW
Rated operational power at AC-53A, 380/400 V, 50 Hz3 kW
Rated operational voltage42 - 550 V; 500 V AC
Switching level19.2 - 30 V DC, Switching level "High", Actuating circuit (ON, L, R); < 5 V DC, Switching level "confirm Off", Actuating circuit (ON, L, R); -3 - 9.6 V DC, Switching level "Low", Actuating circuit (ON, L, R)
Radio interference classEN 55011; Class A (EN 61000-6-3, emitted interference, radiated)
ClassCLASS 10
Connection to SmartWire-DTYes
Degree of protectionIP20; NEMA Other
ModelDirect starter
Mounting methodTop-hat rail fixing (according to IEC/EN 60715, 35 mm); Rail mounting possible
Mounting positionMotor feeder at bottom; Vertical
Overload release current setting - max9 A
Overload release current setting - min1.5 A
Product categoryElectronic motor starter
ProtocolOther bus systems
Residual ripple≤ 5 % (input voltage)
Terminal capacity0.2 - 2.5 mm², Main cables, Push-in terminals
Terminal capacity (AWG)24 - 14, Push-in terminals
TypeDOL starter (complete device)
Voltage typeDC
Explosion safety category for dustATEX dust-ex-protection, II (2) G [Ex e] [Ex d] [Ex px]; ATEX dust-ex-protection, II (2) D [Ex t] [Ex p]
Safety parameter (EN ISO 13849-1)3, Category; PL e, Performance level; 60 (safe switch off) / 82 (motor protection) years; MTTFD
Safety parameter (IEC 62061)Opening delay [ms]: 200 (safe switch off) / Class 10A (motor protection); 99 % (safe switch off) / 98 % (motor protection), DC
With transformerNo
Power consumption12 W
Rated operation power at AC-3, 400 V1.1 kW
Suitable for emergency stopNo
Rated operation current Ie3 A
Number of indicator lights5
Overload release current setting0.18–3 A
Supporting protocol for LONNo
Supporting protocol for TCP/IPNo
Supporting protocol for ASINo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for other bus systemsYes
External reset possibleYes
Suitable for rail mountingYes
Rated control supply voltage DC24 V
Supporting protocol for SERCOSNo
Supporting protocol for INTERBUS-SafetyNo
Release classCLASS 10
With short-circuit releaseNo
With fuseNo
Type of electrical connection of main circuitSpring clamp connection
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for PROFINET CBANo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Voltage type for actuatingDC
Type of motor starterReversing starter
Rated operation power at AC-3, 230 V, 3-phase0.55 kW
Rated operation current at AC-3, 400 V3 A
Ambient temperature, upper operating limit40 °C
Temperature compensated overload protectionYes
Coordination class according to IEC 60947-4-3Class 1
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents