cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

FAZ-D4/3 (278888)

Eaton · Electrical Components · Miniature Circuit Breakers · Ireland · eaton.com
Part Number
278888  ·  HS 8536.30
FAZ-D4/3 (278888)

Eaton 278888 Industry unit breaker 3pol 4A D curve.

Technical Specifications

Manufacturer part number (MPN)278888
EAN / GTIN4015082788889
Sales unitpcs
Package quantity40 pcs
Eaton catalogue number278888
Depth80 mm
Height75.5 mm
Width54 mm
Weight0.338 kg
CompliancesUL CSA09 (with supplementary protector only); RoHS conform
CertificationsNorth America (UL recognized, CSA certified); CSA-C22.2 No. 235; IEC/EN 60898; UL 1077; CE marking; UL (Category Control Number QVNU2, QVNU8); UL (File No. E177451); CSA (Class No. 3215-30); CSA (File No. 204453); IEC/EN 60947-2; EN45545-2; IEC 61373
Current limiting class3
FeaturesAdditional equipment possible
Special featuresAmbient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Used withMiniature circuit breaker; FAZ
Amperage Rating4 A
ApplicationBranch circuits, not as BCPD Switchgear for industrial and advanced commercial applications xEffect - Switchgear for industrial and advanced commercial applications
Number of polesThree-pole
Number of poles (protected)3
Number of poles (total)3
Release characteristicD
Tripping characteristicD
TypeFAZ Miniature circuit breaker
Ambient operating temperature - max75 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent4.4 W
Rated operational current for specified heat dissipation (In)4 A
Frequency rating - max60 Hz
Frequency rating - min50 Hz
Overvoltage categoryIII
Pollution degree2
Rated impulse withstand voltage (Uimp)4 kV
Rated insulation voltage (Ui)440 V
Rated operational voltage (Ue) - max400 V
Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V10 kA
Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V10 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V15 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V15 kA
Rated switching capacity (IEC/EN 60947-2)15 kA
Voltage rating240 V AC / 415 V AC
Voltage rating (UL CSA 13)480 Y/277 V AC
Voltage typeAC
Built-in depth70.5 mm
Connectable conductor cross section (multi-wired) - max25 mm²
Connectable conductor cross section (multi-wired) - min1 mm²
Connectable conductor cross section (solid-core) - max25 mm²
Connectable conductor cross section (solid-core) - min1 mm²
Degree of protectionIP20 (IEC); UL/CSA Type: -; IP20
Width in number of modular spacings3
Document NameDescription Action
Power loss4.5 W
Number of protected poles3
Rated current4 A
Rated voltage400 V
Rated insulation voltage Ui440 V
Rated impulse withstand voltage Uimp4 kV
Frequency50–60 Hz
Concurrently switching neutral conductorNo
Additional equipment possibleYes
Ambient temperature during operating-25–75 °C
Connectable conductor cross section multi-wired1–25 mm²
Connectable conductor cross section solid-core1–25 mm²
Explosion-proofNo
Flush-mounted installationNo
Country of originRomania

Properties

MOQ1

Cross-References

Attached Documents