| Manufacturer | Eaton |
| Product family | xEffect FAZ |
| Type designation | FAZ-D30/2 |
| Manufacturer part number (MPN) | FAZ-D30/2 |
| EAN / GTIN | 4015081639700 |
| Eaton / SAP material no. | 1200607200 |
| Poles | 2P |
| Tripping characteristic | Type D |
| Rated current In | 30 A |
| Rated ultimate breaking capacity Icu | 15 kA |
| Rated operational voltage Ue | 230/400 V AC |
| Mounting | DIN rail (35 mm) |
| Standard | IEC/EN 60947-2 |
| HS code | 8536.20 |
| Sales unit | pcs |
| Eaton catalogue number | 167492 |
| Depth | 80 mm |
| Height | 75.5 mm |
| Width | 36 mm |
| Weight | 0.237 kg |
| Compliances | RoHS conform |
| Certifications | IEC 60947-2; CSA Std. C22.2 No.235; UL 1077; EN45545-2; IEC 61373 |
| Catalog Notes | Magnetic range for higher startup inrush levels that are usually seen in motors and transformers, and other high inductive systems. |
| Current limiting class | 3 |
| Features | Additional equipment possible |
| Special features | Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity |
| Used with | FAZ; Miniature circuit breaker |
| Amperage Rating | 30 A |
| Application | Switchgear for industrial and advanced commercial applications xEffect - Switchgear for industrial and advanced commercial applications |
| Number of poles | Two-pole |
| Number of poles (protected) | 2 |
| Number of poles (total) | 2 |
| Release characteristic | D |
| Type | FAZ Miniature circuit breaker |
| Ambient operating temperature - max | 75 °C |
| Ambient operating temperature - min | -25 °C |
| Equipment heat dissipation, current-dependent | 5.4 W |
| Heat dissipation capacity | 0 W |
| Heat dissipation per pole, current-dependent | 0 W |
| Rated operational current for specified heat dissipation (In) | 30 A |
| Static heat dissipation, non-current-dependent | 0 W |
| Frequency rating - max | 60 Hz |
| Frequency rating - min | 50 Hz |
| Overvoltage category | III |
| Pollution degree | 2 |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated insulation voltage (Ui) | 440 V |
| Rated operational voltage (Ue) - max | 415 V |
| Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V | 10 kA |
| Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V | 10 kA |
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V | 15 kA |
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V | 15 kA |
| Rated switching capacity (IEC/EN 60947-2) | 15 kA |
| Voltage type | AC |
| Built-in depth | 70.5 mm |
| Connectable conductor cross section (multi-wired) - max | 25 mm² |
| Connectable conductor cross section (multi-wired) - min | 1 mm² |
| Connectable conductor cross section (solid-core) - max | 25 mm² |
| Connectable conductor cross section (solid-core) - min | 1 mm² |
| Degree of protection | IP20 |
| Width in number of modular spacings | 2 |
| Document Name | Description Action |