cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton xEffect FRCdM Residual Current Circuit Breaker (RCCB) — Type Bfq, 4-Pole, 40 A, 300 mA, Short-Time Delayed (167905)

Eaton · Electrical Components · RCDs & RCBOs · Ireland · eaton.com
Part Number
167905  ·  HS 8536.90
Eaton xEffect FRCdM Residual Current Circuit Breaker (RCCB) — Type Bfq, 4-Pole, 40 A, 300 mA, Short-Time Delayed (167905)

The Eaton 167905 is a residual current circuit breaker (RCCB) from the Moeller series xEffect FRCdM range. It disconnects the circuit when the current flowing out does not match the current returning — the signature of a fault to earth, whether through failed insulation or through a person. It provides no overcurrent protection of its own and is installed together with the circuit's MCB or fuse. This device is 4-pole, rated 40 A, with a rated residual current of 300 mA. Type Bfq is Eaton's type B variant with a tripping curve adapted to reliably sense residual currents up to 50 kHz. It is the frequency-converter type, for installations whose normal operating leakage is itself high-frequency and would otherwise cause nuisance tripping or, worse, mask a real fault. Bfq and B+ are not interchangeable: B+ is chosen for fire protection, Bfq for drive-heavy installations. It is the G (short-time delayed) version, which rides through the brief leakage surges that switching and cable capacitance produce at energisation instead of tripping on them. At 300 mA it is intended for protection against earth-fault fire and for equipment protection, not for protection against direct contact — that requires a 30 mA device. Supplied by cBallast on quote-to-invoice terms; lead time and freight are quoted per RFQ against the destination Incoterm.

Technical Specifications

Manufacturer part number (MPN)167905
EAN / GTIN4015081644803
HS code8536.90
Sales unitpcs
Package quantity30 pcs
Eaton catalogue number167905
Depth76 mm
Height80 mm
Width70 mm
Weight0.32 kg
CompliancesRoHS conform
CertificationsIEC/EN 61008; IEC/EN 62423; EN45545-2; IEC 61373; ÖVE E 8601
FeaturesResidual current circuit-breakers, digital; Additional equipment possible; Selective protection
Fitted withInterlocking device
FunctionsShort-time delayed tripping
Special featuresFRCdM Residual current circuit-breakers, digital Type G/Bfq (ÖVE E 8601)
Used withResidual current circuit-breakers, digital; Type G/Bfq (�VE E 8601); FRCdM
Amperage Rating40 A
ApplicationxEffect - Switchgear for industrial and advanced commercial applications
Fault current rating300 mA
Impulse withstand current3 kA (8/20 μs) surge-proof
Number of polesFour-pole
Rated short-circuit strength10 kA
Sensitivity typeAll current sensitive - frequency converter-proof
Tripping time10 ms delayed; Short time-delayed
Ambient operating temperature - max50 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent6.2 W
Heat dissipation capacity6.2 W
Heat dissipation per pole, current-dependent1.55 W
Rated operational current for specified heat dissipation (In)40 A
Static heat dissipation, non-current-dependent0 W
Admissible back-up fuse63 A gG/gL
Admissible back-up fuse overload - max40 A gG/gL
Frequency rating50 Hz
Leakage current typeB
Lifespan, electrical4000 operations
Pollution degree2
Radiation resistanceSuitable for variable frequency drives (enhanced sensitivity)
Rated fault current - max0.3 A
Rated fault current - min0.3 A
Rated impulse withstand voltage (Uimp)4 kV
Rated insulation voltage (Ui)440 V
Rated operational voltage (Ue) - max415 V
Rated residual making and breaking capacity500 A
Rated short-time withstand current (Icw)10 kA
Short-circuit rating63 A (max. admissible back-up fuse)
Surge current capacity3 kA
Test circuit range196 V AC - 456 V AC
Voltage rating - max456 VAC
Voltage rating - min50 VAC
Voltage rating (IEC/EN 60947-2)240 V AC / 415 V AC
Switching capacity of auxiliary contact - min10 μA, 10 mV DC
Switching current of auxiliary contact - max2 A
Switching duty with resistive load of auxiliary contact - max60 W
Switching voltage at AC of auxiliary contact - max240 V
Switching voltage at DC of auxiliary contact - max220 V
Terminal capacity of auxiliary contact0.25 mm² - 1.5 mm²
Built-in depth70.5 mm
Built-in width (number of units)70 mm (4 SU)
Busbar material thickness0.8 mm - 2 mm
Climatic proofing25-55 °C / 90-95% relative humidity according to IEC 60068-2
Connectable conductor cross section (multi-wired) - max16 mm²
Connectable conductor cross section (multi-wired) - min1.5 mm²
Connectable conductor cross section (solid-core) - max35 mm²
Connectable conductor cross section (solid-core) - min1.5 mm²
Contact position indicator colorRed / green
Degree of protectionIP20; IP20, IP40 with suitable enclosure
Frame45 mm
Lifespan, mechanical20000 operations
Mounting MethodDIN rail; Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Mounting positionAs required
Permitted storage and transport temperature - max60 °C
Permitted storage and transport temperature - min-35 °C
Status indicationWhite / blue
Terminal capacity (cable)M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2)
Terminal capacity (solid wire)1.5 mm² - 35 mm²
Terminal capacity (stranded cable)16 mm² (2x)
Terminal protectionFinger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)Twin-purpose terminals
Tightening torque2 Nm - 2.4 Nm
Width in number of modular spacings4
Product familyEaton Moeller series xEffect FRCdM RCCB
Device typeResidual current circuit breaker (RCCB), no integral overcurrent protection
Residual current typeType Bfq
Rated residual current (IΔn)300 mA
Rated current40 A
Tripping characteristicShort-Time Delayed (G)
Selection noteFrequency-converter variant — reliable sensing up to 50 kHz
Protection purposeProtection against earth-fault fire / equipment protection

Properties

MOQ1

Cross-References

Attached Documents