cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Residual Current Circuit Breaker G/B 40A/4/30MA (FRCDM-40/4/003-G/B)

Eaton · Electrical Components · RCDs & RCBOs · Ireland · eaton.com
Part Number
FRCDM-40/4/003-G/B  ·  HS 8536.90
Residual Current Circuit Breaker G/B 40A/4/30MA (FRCDM-40/4/003-G/B)

digital residual current circuit breaker. B-type; can be used in all mains/network systems.

Technical Specifications

Manufacturer part number (MPN)FRCDM-40/4/003-G/B
EAN / GTIN4015081644698
HS code8536.90
Sales unitpcs
Package quantity30 pcs
Eaton catalogue number167893
Depth76 mm
Height80 mm
Width70 mm
Weight0.32 kg
CompliancesRoHS conform
CertificationsIEC/EN 62423; IEC/EN 61008; ÖVE E 8601; EN45545-2; IEC 61373
FeaturesResidual current circuit-breakers, digital; Additional equipment possible; Selective protection
Fitted withInterlocking device
FunctionsShort-time delayed tripping
Used withResidual current circuit-breakers, digital; FRCdM; Type G/B (ÖVE E 8601)
Amperage Rating40 A
ApplicationxEffect - Switchgear for industrial and advanced commercial applications
Fault current rating30 mA
Impulse withstand current3 kA (8/20 μs) surge-proof
Number of polesFour-pole
Rated short-circuit strength10 kA
Sensitivity typeAll current sensitive
Tripping time10 ms delayed; Short time-delayed
TypeFRCdM Residual current circuit-breakers, digital Type G/B (ÖVE E 8601)
Ambient operating temperature - max60 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent6.2 W
Heat dissipation capacity6.2 W
Heat dissipation per pole, current-dependent0 W
Rated operational current for specified heat dissipation (In)40 A
Static heat dissipation, non-current-dependent0 W
Admissible back-up fuse63 A gG/gL
Admissible back-up fuse overload - max40 A gG/gL
Frequency rating50 Hz
Leakage current typeB
Lifespan, electrical4000 operations
Pollution degree2
Rated fault current - max0.03 A
Rated fault current - min0.03 A
Rated impulse withstand voltage (Uimp)4 kV
Rated insulation voltage (Ui)440 V
Rated operational voltage (Ue) - max415 V
Rated residual making and breaking capacity500 A
Rated short-time withstand current (Icw)10 kA
Short-circuit rating63 A (max. admissible back-up fuse)
Surge current capacity3 kA
Test circuit range196 V AC - 264 V AC
Voltage rating - max456 VAC
Voltage rating - min50 VAC
Voltage rating (IEC/EN 60947-2)240 V AC / 415 V AC
Switching capacity of auxiliary contact - min10 μA, 10 mV DC
Switching current of auxiliary contact - max2 A
Switching duty with resistive load of auxiliary contact - max60 W
Switching voltage at AC of auxiliary contact - max240 V
Switching voltage at DC of auxiliary contact - max220 V
Terminal capacity of auxiliary contact0.25 mm² - 1.5 mm²
Built-in depth70.5 mm
Built-in width (number of units)70 mm (4 SU)
Busbar material thickness0.8 mm - 2 mm
Climatic proofing25-55 °C / 90-95% relative humidity according to IEC 60068-2
Connectable conductor cross section (multi-wired) - max16 mm²
Connectable conductor cross section (multi-wired) - min1.5 mm²
Connectable conductor cross section (solid-core) - max35 mm²
Connectable conductor cross section (solid-core) - min1.5 mm²
Contact position indicator colorRed / green
Degree of protectionIP20, IP40 with suitable enclosure; IP20
Frame45 mm
Lifespan, mechanical20000 operations
Mounting MethodDIN rail; Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Mounting positionAs required
Permitted storage and transport temperature - max60 °C
Permitted storage and transport temperature - min-35 °C
Status indicationWhite / blue
Terminal capacity (cable)M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2)
Terminal capacity (solid wire)1.5 mm² - 35 mm²
Terminal capacity (stranded cable)16 mm² (2x)
Terminal protectionFinger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)Twin-purpose terminals
Tightening torque2 Nm - 2.4 Nm
Width in number of modular spacings4

Properties

MOQ1

Cross-References

Attached Documents