| Manufacturer part number (MPN) | mRB6-16/3N/C/003-A |
| EAN / GTIN | 4015081184903 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 30 pcs |
| Eaton catalogue number | 120660 |
| Depth | 80 mm |
| Height | 75.5 mm |
| Width | 70 mm |
| Weight | 0.445 kg |
| Compliances | RoHS conform |
| Certifications | CE |
| Current limiting class | 3 |
| Features | Concurrently switching N-neutral |
| Standards | IEC/EN 61009 |
| Application | Switchgear for residential and commercial applications |
| Basic function | Combined RCD/MCB devices |
| Fault current rating | 0.03 A |
| Number of poles | Three-pole + N |
| Number of poles (protected) | 4 |
| Number of poles (total) | 4 |
| Product application | Switchgear for industrial and advanced commercial applications |
| Product range | mRB6 |
| Rated current | 16 A |
| Rated current of product range | 6 - 25 Ampere |
| Release characteristic | C |
| Sensitivity type | Type A, pulse-current sensitive |
| Tripping characteristic | C |
| Type | RCBO |
| Ambient operating temperature - max | 40 °C |
| Ambient operating temperature - min | -25 °C |
| Equipment heat dissipation, current-dependent | 10.9 W |
| Heat dissipation capacity | 0 W |
| Heat dissipation per pole, current-dependent | 0 W |
| Rated operational current for specified heat dissipation (In) | 16 A |
| Static heat dissipation, non-current-dependent | 0 W |
| Back-up fuse | 100 Ampere gL |
| Disconnection characteristic | Undelayed |
| Frequency rating | 50 Hz |
| Impulse withstand current | Partly surge-proof, 250 A |
| Leakage current type | A |
| Pollution degree | 2 |
| Rated fault currents of product range | 30, 100, 300 MilliAmpere |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated insulation voltage (Ui) | 500 V |
| Rated non-tripping current | 0.5 x I∆n |
| Rated operational voltage (Ue) - max | 400 V |
| Rated short-circuit breaking capacity (EN 60947-2) | 6 kA |
| Rated short-circuit breaking capacity (EN 61009-1) | 6 kA |
| Rated short-circuit breaking capacity (EN 61009) | 6 kA |
| Rated switching capacity | 6 kA |
| Rated switching capacity (IEC/EN 60947-2) | 6 kA |
| Rated switching capacity (IEC/EN 61009) | 6 kA |
| Selectivity class | 3 |
| Surge current capacity | 0.25 kA |
| Tripping | Non-delayed |
| Voltage rating | 400 V |
| Voltage rating at AC | 230 V / 400 V |
| Voltage type | AC |
| Built-in depth | 70 mm |
| Climatic proofing | IEC 68-2: 25 °C - 55 °C at 90 % - 95 % humidity |
| Connectable conductor cross section (multi-wired) - max | 25 mm² |
| Connectable conductor cross section (multi-wired) - min | 1 mm² |
| Connectable conductor cross section (solid-core) - max | 25 mm² |
| Connectable conductor cross section (solid-core) - min | 1 mm² |
| Degree of protection | IP20 |
| Degree of protection (built in) | IP40 |
| Device height | 80 mm |
| Frame | 45 mm |
| Material thickness | 2 mm |
| Mounting Method | DIN rail |
| Mounting style | Tri-stable slide catch - enables removal from existing busbar combination |
| Solid terminal capacities | 1 - 25 Square Millimeter |
| Terminal protection | Busbar tag shroud to VBG4 |
| Terminals (top and bottom) | Twin-purpose |
| Width in number of modular spacings | 4 |