| Manufacturer | Eaton |
| Product family | xEffect FAZ |
| Type designation | FAZ-OV63/3 |
| Manufacturer part number (MPN) | FAZ-OV63/3 |
| EAN / GTIN | 9010238117914 |
| El-nummer (NO) | 1624153 |
| Poles | 3P |
| Release | thermomagnetic (overload + short-circuit) |
| Rated current In | 63 A |
| Rated ultimate breaking capacity Icu | 15 kA |
| Rated operational voltage Ue | 230/400 V AC |
| Mounting | DIN rail (35 mm) |
| Standard | IEC/EN 60947-2 |
| HS code | 8536.20 |
| Sales unit | pcs |
| Eaton catalogue number | 300360 |
| Depth | 72.6 mm |
| Height | 80 mm |
| Width | 53.1 mm |
| Weight | 0.369 kg |
| Compliances | RoHS conform |
| Current limiting class | 3 |
| Features | Additional equipment possible |
| Suitable for | Flush-mounted installation |
| Amperage Rating | 63 A |
| Number of poles (protected) | 3 |
| Number of poles (total) | 3 |
| Release characteristic | Other |
| Ambient operating temperature - max | 55 °C |
| Ambient operating temperature - min | -20 °C |
| Frequency rating - max | 60 Hz |
| Frequency rating - min | 50 Hz |
| Overvoltage category | III |
| Pollution degree | 2 |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated insulation voltage (Ui) | 440 V |
| Rated operational voltage (Ue) - max | 230 V |
| Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V | 10 kA |
| Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V | 10 kA |
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V | 15 kA |
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V | 15 kA |
| Voltage type | AC |
| Built-in depth | 60 mm |
| Connectable conductor cross section (multi-wired) - max | 16 mm² |
| Connectable conductor cross section (multi-wired) - min | 2 mm² |
| Connectable conductor cross section (solid-core) - max | 35 mm² |
| Connectable conductor cross section (solid-core) - min | 1.5 mm² |
| Degree of protection | IP20 |
| Width in number of modular spacings | 3 |
| Document Name | Description Action |