| Manufacturer part number (MPN) | PDIM-100/4 |
| EAN / GTIN | 4015081113118 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 30 pcs |
| Eaton catalogue number | 111761 |
| Depth | 76 mm |
| Height | 80 mm |
| Width | 70 mm |
| Weight | 0.404 kg |
| Compliances | RoHS conform |
| Certifications | DIN/EN 62020 |
| Used with | Leakage current monitor; PDIM |
| Amperage Rating | 100 A |
| Features | Additional equipment possible; Leakage current monitor; Selective protection |
| Fitted with | Interlocking device |
| Frame | 45 mm |
| Frequency rating | 60 Hz |
| Pollution degree | 2 |
| Lifespan, mechanical | 20000 operations |
| Mounting Method | Quick attachment with 2 latch positions on top-hat rail IEC/EN 60715; DIN rail |
| Climatic proofing | 25-55 °C / 90-95% relative humidity according to IEC 60068-2 |
| Equipment heat dissipation, current-dependent | 18.8 W |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated short-time withstand current (Icw) | 10 kA |
| Admissible back-up fuse overload - max | 63 A gG/gL |
| Built-in width (number of units) | 70 mm (4 SU) |
| Busbar material thickness | 0.8 mm - 2 mm |
| Short-circuit rating | 100 A (max. admissible back-up fuse) |
| Terminal protection | Finger and hand touch safe, DGUV VS3, EN 50274 |
| Terminals (top and bottom) | Twin-purpose terminals |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature - min | -25 °C |
| Built-in depth | 60 mm |
| Connectable conductor cross section (multi-wired) - max | 16 mm² |
| Connectable conductor cross section (multi-wired) - min | 1.5 mm² |
| Connectable conductor cross section (solid-core) - max | 35 mm² |
| Connectable conductor cross section (solid-core) - min | 1.5 mm² |
| Fault current rating | 1000 mA |
| Heat dissipation capacity | 0 W |
| Heat dissipation per pole, current-dependent | 0 W |
| Permitted storage and transport temperature - max | 60 °C |
| Permitted storage and transport temperature - min | -35 °C |
| Degree of protection | IP20; IP20, IP40 with suitable enclosure |
| Number of poles | Four-pole |
| Leakage current type | AC |
| Lifespan, electrical | 4000 operations |
| Type | Leakage current monitor PDIM |
| Special features | Current test marks as per inscription Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C Switching contact (potential-free) 10 A / 240 V~ |
| Application | Switchgear for industrial and advanced commercial applications xEffect - Switchgear for industrial and advanced commercial applications |
| Functions | Short-time delayed tripping; Fault current adjustable: 0.03 A/0.1 A/0.3 A/0.5 A/1 A |
| Sensitivity type | AC and pulsating DC current sensitive |
| Rated fault current - max | 1 A |
| Rated fault current - min | 0.03 A |
| Rated insulation voltage (Ui) | 440 V |
| Rated operational current for specified heat dissipation (In) | 100 A |
| Rated operational voltage (Ue) - max | 415 V |
| Static heat dissipation, non-current-dependent | 0 W |
| Surge current capacity | 0.25 kA |
| Width in number of modular spacings | 4 |
| Voltage rating (IEC/EN 60947-2) | 230/400 V, 50/60 Hz 240/415 V, 50/60 Hz |
| Voltage type | AC |
| Terminal capacity (solid wire) | 1.5 mm² - 35 mm² |
| Tripping time | Non-delayed, adjustable; Selective switch off, adjustable; 40 ms delayed, selective (type S); 10 ms delayed (Type G); Short time-delayed, adjustable |
| Terminal capacity (control cable) | 0.25 mm² - 1.5 mm² at switching contacts |
| Rated short-circuit strength | 10 kA |
| Response behavior (adjustable) | Undelayed |
| Response behavior of contacts | 1: 30 - 50 % Iδn; 2: > 50 % IΔn |
| Terminal capacity (stranded cable) | 16 mm² (2x) |
| RAL-number | 7035 |
| Color | Gray |