cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Safety Switch (DMV-250/3/M4/P-R)

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
DMV-250/3/M4/P-R  ·  HS 8536.50
Safety Switch (DMV-250/3/M4/P-R)

Technical Specifications

Manufacturer part number (MPN)DMV-250/3/M4/P-R
EAN / GTIN8711426210035
Sales unitpcs
Eaton catalogue number6094966
Depth63 mm
Height135 mm
Width205 mm
Weight1.6 kg
CertificationsIEC/EN 60204; CE; KEMA; RoHS; Lloyds; IEC/EN 60947; EAC; VDE 0660; IEC/EN 60947-3
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-30 °C
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid4.5 W
Heat dissipation per pole, current-dependent Pvid3.75 W
Rated operational current for specified heat dissipation (In)250 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)2000 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)1760 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)1120 A
Rated insulation voltage (Ui)1000 V
Rated operational current (Ie) at AC-21, 400 V, 415 V250 A
Rated operational current (Ie) at AC-21, 500 V250 A
Rated operational current (Ie) at AC-21, 690 V250 A
Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V250 A
Rated operational current (Ie) at AC-22, 500 V250 A
Rated operational current (Ie) at AC-22, 690 V250 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V250 A
Rated operational current (Ie) at AC-23A, 500 V220 A
Rated operational current (Ie) at AC-23A, 690 V140 A
Rated operational power at AC-23A, 400 V, 50 Hz250 kW
Rated operational power at AC-23A, 500 V, 50 Hz160 kW
Rated operational power at AC-23A, 690 V, 50 Hz132 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)250 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FeaturesVersion as main switch; Version as emergency stop installation; Version as maintenance-/service switch; Version as safety switch
Fitted withRed rotary handle and yellow locking ring
FunctionsInterlockable; Emergency switching off function
Locking facilityLockable in the 0 (Off) position
Locking mechanismPadlocking feature SVC
Number of polesThree-pole
AccessoriesAuxiliary contact fitted by user.
Actuator colorRed
Actuator typeLong turning handle
Connection type9 mm connection hole
Degree of protectionNEMA Other
Degree of protection (front side)IP20
Lifespan, mechanical10,000 Operations
Mounting methodRear mounting
Mounting positionAs required
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch Switch-disconnector
Rated impulse withstand voltage (Uimp)8000 V
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Suitable forIntermediate mounting; Ground mounting
Switching angle90 °
Breaking current40 kA (at In = 500); 33 kA (at In = 250)
Light-through energyMax. 380 kA²s (at In = 250); Max. 1700 kA²s (at In = 500)
Rated conditional short-circuit current (Iq)100 kA at In = 250; 50 kA
Rated short-time withstand current (Icw)12 kA; 12 kA, Contacts, 1 second
Short-circuit protection rating500/250, Fuse, Contacts
Screw sizeM8 x 20, Terminal screw
Stripping length (main cable)21 mm
Terminal capacity120 mm², Flat conductor connection with busbars
Tightening torque14 Nm, Screw terminals
Country of originNetherlands

Properties

MOQ1

Cross-References

Attached Documents