cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss orifice assembly no. 02 for TE 5 thermostatic expansion valve (code 067B2790)

Danfoss · HVAC & Refrigeration · Expansion Valves · Denmark · danfoss.com
Part Number
067B2790  ·  HS 8481.90
Danfoss orifice assembly no. 02 for TE 5 thermostatic expansion valve (code 067B2790)

Danfoss interchangeable orifice assembly (ORF) no. 02 for the TE 5 thermostatic expansion valve. R134a 16 kW, R22 25 kW, R407C 25 kW, R407F 28 kW, R404A/R507A 19 kW, R1234yf 14 kW. Compatible refrigerants: R22, R134a, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R455A, R513A, R1234yf. Fits the TE 5 valve body of the TE parts program.

Technical Specifications

TypeOrifice assembly (ORF, thermostatic expansion valve)
Used forTE 5
Orifice no.02
RefrigerantsR22, R134a, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R455A, R513A, R1234yf
Rated capacity (Range N)R134a 16 kW, R22 25 kW, R407C 25 kW, R407F 28 kW, R404A/R507A 19 kW, R1234yf 14 kW
Rating basiste 4.4 °C, tc 38 °C, tliq 37 °C (ARI)
Net weight0.101 kg / Gross: 0.134 kg
EAN5702428320979
Code number067B2790
Product groupExpansion valves
Orifice size02
ApprovalEAC; LLC CDC TYSK
REACH candidate-list substancesLead (CAS no. 7439-92-1)
Rated cap. cond. Range N [IMP]tcond=100 °F; tevap=40 °F; tliq=98 °F
Rated cap. R134a
Range N16.00 kW, 4.50 TR
Rated cap. R22
Range B16.70 kW, 4.76 TR
Rated cap. R22
Range N25.00 kW, 7.00 TR
Rated cap. R404A
Range B10.90 kW, 3.09 TR
Rated cap. R404A
Range N19.00 kW, 5.50 TR
Rated cap. R407A
Range N25.00 kW, 7.00 TR
Rated cap. R407C
Range N25.00 kW, 7.00 TR
Rated cap. R407F
Range N28.00 kW, 8.00 TR
Rated cap. R454C
Range N23.27 kW, 6.63 TR
Rated cap. R507
Range B10.90 kW, 3.09 TR
Rated cap. R507
Range N19.00 kW, 5.50 TR
Rated cap.R1234yf, Range N [kW14.00 kW
Rated cap.R1234yf, Range N [TR4.00 TR
EU RoHS complianceYes with exemptions

Properties

MOQ1

Compatibility

For the Danfoss TE 5 / TE 12 / TE 20 thermostatic expansion valve parts program. Match refrigerant, orifice/element and body to the same valve size. Verify against your system specification.

Standards

Approvals

Attached Documents