Danfoss exchangeable thermostatic power element for the TE 12 expansion valve, charged for R22/R407C. Externally equalized via a 1/4 in flare connection. Maximum operating pressure limit MOP 20 charge (MOP point at -20 °C). Evaporating temperature range -60 to -25 °C. 3000 mm (118 in) capillary tube. Max working pressure 28 bar (400 psig). Laser-welded stainless steel element, capillary tube and bulb; brass body. Supplied with bulb strap.
| Type | Power element (thermostatic element, exchangeable) |
| Used for | TE 12 |
| Refrigerant | R22/R407C |
| Pressure equalization | externally equalized |
| MOP | MOP 20 charge (MOP point at -20 °C) |
| Evaporating temperature range | -60 to -25 °C |
| Max working pressure | 28 bar (400 psig) |
| Capillary tube | 3000 mm |
| Equalization connection | 1/4 in flare |
| Element/capillary/bulb | Laser-welded stainless steel; brass body |
| Net weight | 0.56 kg |
| EAN | 5702428149211 |
| Compatible with | TE 12 thermostatic expansion valve |
| MPN | 067B3211 |
| Product group | Expansion valves |
| Approval | EAC |
| Body material | Brass |
| Capillary tube length [in] | 118 in |
| Capillary tube length [mm] | 3000 mm |
| China RoHS compliance | Yes |
| Equalization connection type | Flare |
| Equalization size [in] | 1/4 in |
| EU RoHS compliance | Out of scope |
| Max. Working Pressure [bar] | 28 bar |
| Max. Working Pressure [psig] | 400 psig |
| MOP Point [psig] | MOP 20 |
| MOP Point [°C] | -20 °C |
| MOP Point [°F] | -5 °F |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Refrigerants | R22/R407C |
| Temperature range [°C] [max] | -25 °C |
| Temperature range [°C] [min] | -60 °C |
| Temperature range [°F] [max] | -15 °F |
| Temperature range [°F] [min] | -75 °F |
| Type designation | Element |
| MOQ | 1 |
For the Danfoss TE 5 / TE 12 / TE 20 / TE 55 thermostatic expansion valve parts program. Match refrigerant, orifice/element and body to the same valve size. Verify against your system specification.