Danfoss TE 55 orifice assembly No. 9B (type ORF), OEM order code 067G2705. The orifice (nozzle) is the interchangeable metering element that sets the throttling capacity of the TE 55 / TQ 55 thermostatic expansion valve; it seats in the valve body (067G4001-4004) and is sized by orifice number to the system refrigerating capacity. Balanced port for stable regulation across load. Rated capacities per refrigerant are listed below (Range N unless noted). Compatible with R134a, R22, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R513A. Data quoted verbatim from store.danfoss.com (code 067G2705).
| Brand | Danfoss |
| Part number | 067G2705 |
| Type | ORF (orifice assembly / interchangeable nozzle) |
| Used for | TE 55 / TQ 55 thermostatic expansion valves |
| Orifice size (number) | 9B |
| Balanced port | Yes |
| Refrigerant compatibility | R134a, R22, R404A/R507A, R407A, R407C, R407F, R448A, R449A, R452A, R513A |
| Rated capacity R134a (Range N) | 74 kW / 21 TR |
| Rated capacity R22 (Range N) | 113 kW / 32 TR |
| Rated capacity R407C (Range N) | 109 kW / 31 TR |
| Net weight | 0.25 kg |
| Gross weight | 0.282 kg |
| Packing | 8 pc per multi-pack |
| EAN | 5702428434164 |
| Approvals | EAC, LLC CDC TYSK |
| HS code | 8481.90 (valve parts) |
| Product group | Expansion valves |
| Approval | EAC |
| Balanced port [Yes/No] | Yes |
| China RoHS compliance | Out of scope |
| EU RoHS compliance | Yes with exemptions |
| EU RoHS exemption clause | 6(a) |
| Orifice size | 9B |
| Rated cap. cond. Range N [IMP] | tcond=100 °F |
| Rated cap. cond. Range N [SI] | tconc=38 °C |
| Rated cap. R134a, Range N [kW] | 74 kW |
| Rated cap. R134a, Range N [TR] | 21 TR |
| Rated cap. R22, Range B [kW] | 66.2 kW |
| Rated cap. R22, Range B [TR] | 18.8 TR |
| Rated cap. R22, Range N [kW] | 113 kW |
| Rated cap. R22, Range N [TR] | 32 TR |
| Rated cap. R404A, Range B [kW] | 43.2 kW |
| Rated cap. R404A, Range B [TR] | 12.3 TR |
| Rated cap. R404A, Range N [kW] | 84 kW |
| Rated cap. R404A, Range N [TR] | 24 TR |
| Rated cap. R407A, Range N [kW] | 109 kW |
| Rated cap. R407A, Range N [TR] | 31 TR |
| Rated cap. R407C, Range N [kW] | 109 kW |
| Rated cap. R407C, Range N [TR] | 31 TR |
| Rated cap. R407F, Range N [kW] | 123 kW |
| Rated cap. R407F, Range N [TR] | 35 TR |
| Rated cap. R507, Range B [kW] | 43.2 kW |
| Rated cap. R507, Range B [TR] | 12.3 TR |
| Rated cap. R507, Range N [kW] | 84 kW |
| Rated cap. R507, Range N [TR] | 24 TR |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Refrigerants | R134a |
| Used for product | TE 55 |
| Material | Brass orifice / nozzle assembly (balanced port) |
| Primary standard | EN 12284 |
| MOQ | 1 |