cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss RT260A Differential Pressure Switch 0.5 to 4 bar SPDT Manual Max Reset G3/8 (017D002266)

Danfoss · Sensors & Instrumentation · Differential Pressure Sensors · Denmark · danfoss.com
Part Number
017D002266  ·  HS 9032.20
Danfoss RT260A Differential Pressure Switch 0.5 to 4 bar SPDT Manual Max Reset G3/8 (017D002266)

Danfoss RT260A mechanical differential pressure switch with bellows sensing element, SPDT contact and manual maximum reset (lockout on high differential). Differential setting range 0.5 to 4 bar; G 3/8 male pressure connection (ISO 228-1); enclosure IP54. Danfoss code number 017D002266.

Technical Specifications

BrandDanfoss
ModelRT260A differential pressure switch
Code number017D002266
Differential pressure range0.5 to 4 bar (0.05 to 0.4 MPa; 7 to 58 psi)
Maximum working pressure22 bar
Contact functionSPDT
ResetManual maximum
Contact differential0.3 bar
Pressure sensing elementbellows
Pressure connectionG 3/8 male (ISO 228-1)
EnclosureIP54
Ambient temperature range-40 to +70 degC
Contact ratingAC15=3 A at 400 V; AC1=10 A at 400 V; AC3=4 A at 400 V; DC13=12 W at 220 V; LR=28 A at 400 V
StandardsEN 60947-4, EN 60947-5
ApprovalsCE, EAC, CCC, CMIM, KR, RINA, RMRS
EAN5702428042833
Net weight1.006 Kilogram
TypeRT260A
Product groupSwitches and thermostats
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-50 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-58 °F
ApprovalCCC
CE markYes
China RoHS complianceYes
Contact differential [bar]0.3 bar
Diff.press.setting range [bar] [max]4 bar
Diff.press.setting range [bar] [min]0.5 bar
Diff.press.setting range [MPa] [max]0.4 MPa
Diff.press.setting range [MPa] [min]0.05 MPa
Diff.press.setting range [psi] [max]58 psi
Diff.press.setting range [psi] [min]7 psi
EEE category5 small equipment (any external dimension < 50 cm)
Electrical conn
Male/FemaleFemale
Electrical connectionScrewed cable entry
Electrical connection size2xPg 13.5
Electrical connection standardDIN 40430
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.2-1.5 mm2
Enclosure rating IPIP54
EU RoHS complianceYes
In scope of WEEEYes
Max. test pressure [bar] Pe25 bar
Max. test pressure [psig]362 psig
Max. Working Pressure [bar]22 bar
Max. Working Pressure [psig]319 psig
Operat. range LP side [bar] Pe [max]18 bar
Operat. range LP side [bar] Pe [min]-1 bar
Operat. range LP side [psig]Pe [max]261 psig
Operat. range LP side [psig]Pe [min]-15 psig
Pressure connection size3/8
Pressure connection standardISO 228-1
Pressure connection typeG
Pressure Male/FemaleMale
Pressure range [bar] Pe [max]18 bar
Pressure range [bar] Pe [min]-1 bar
REACH Candidate List substancesLead (CAS no. 7439-92-1)
RefrigerantsR11
Relay release time [s]0 s
Reset functionManual Max
UL approved refrigerantsR11

Properties

MaterialBellows sensing element
Pressure rating22 bar
Temperature range-40 to +70 degC
IP ratingIP54
Primary standardEN 60947-5
Thread standardISO 8434-1
MOQ1

Compatibility

G 3/8 male (ISO 228-1). Manual maximum reset locks out on high differential. Confirm range against application.

Standards

Approvals

Attached Documents