Danfoss RA-N — thermostatic radiator valve body with presetting for two-pipe hydronic heating systems, OEM order code 013G3322. The RA-N (normal flow) valve body accepts an RA-series thermostatic sensor (RA 2000 / living-eco head) or an actuator on its clamp connection; the integral presetting device limits the design flow per radiator so the system self-balances without a separate balancing valve. Presetting is stepped 1…7 plus fully open (N), read on the scale under the head. Nickel plated brass body, straight pattern. (RA-N 10/15, dimension standard S.) Connection Rp 3/8 (inlet) / R 1/2 (outlet, external for tailpiece), Kvs 0.65 m³/h, max working pressure 10 bar, test pressure 16 bar, max differential pressure 0.6 bar, flow temperature up to 120 °C. Application: 2-pipe system. Net weight 0.21 Kilogram. Genuine Danfoss part; technical data quoted verbatim from store.danfoss.com (code 013G3322). OEM P/N 013G3322, EAN 5702420034119. HS 8481.80.
| Brand | Danfoss |
| Part number | 013G3322 |
| Type | RA-N |
| Product group | Radiator Valves |
| Valve type | Normal flow |
| Design | Straight |
| Valve size | 10/15 |
| Dimension standard | S |
| Connection size (inlet) | Rp 3/8 |
| Connection size (outlet) | R 1/2 |
| Connection types | Internal thread |
| Tailpiece type | Special |
| Presetting | yes |
| Kvs value | 0.65 m³/h |
| Kv at presetting | setting 1 = 0.04 m³/h, setting 2 = 0.08 m³/h, setting 3 = 0.12 m³/h, setting 4 = 0.19 m³/h, setting 5 = 0.25 m³/h, setting 6 = 0.33 m³/h, setting 7 = 0.38 m³/h, setting N = 0.56 m³/h |
| Application | 2-pipe system |
| Flow temperature (max) | 120 °C |
| Working pressure (max) | 10 bar |
| Test pressure | 16 bar |
| Differential pressure (max) | 0.6 bar |
| Finish | Nickel plated |
| REACH candidate-list substances | Lead (CAS no. 7439-92-1) |
| EU RoHS compliance | Yes with exemptions |
| Net weight | 0.21 Kilogram |
| Gross weight | 0.22 Kilogram |
| Packed volume | 0.23 Liter |
| EAN | 5702420034119 |
| HS code | 8481.80 (taps, cocks, valves for pipes, tanks, vats or the like) |
| Material | Body brass, nickel plated |
| Pressure rating | 10 bar max working (test 16 bar) |
| Temperature range | up to 120 °C (flow) |
| MOQ | 1 |
Two-pipe radiator valve body, straight pattern, valve size 10/15, Rp 3/8 inlet / R 1/2 outlet. Accepts a Danfoss RA-series thermostatic sensor (RA 2000 / living eco) or thermal/electric actuator on the valve clamp ring; set the presetting to the design flow of the radiator. Confirm design (Straight), valve size (10/15) and dimension standard (S) against the installation before ordering.