Danfoss RA-KE/KEW manifold assembly, OEM order code 013G3362 — a bare RA-KE/KEW manifold valve body (straight, single-pipe) without an integral return lockshield — it takes a Danfoss RA-series thermostatic sensor or actuator on its clamp connection to throttle the radiator. Used to connect radiators to one-pipe (RA-KE/KEW) or two-pipe (RA-K/KW) Danfoss distribution manifolds. Connection G 1/2 on the manifold side and R 1/2 on the radiator side, straight pattern. Kvs 2.5 m³/h; max working pressure 10 bar (test 16 bar), max differential pressure 0.6 bar, flow temperature up to 120 °C. Brass. Genuine Danfoss part; technical data quoted verbatim from store.danfoss.com (code 013G3362). OEM P/N 013G3362, EAN 5702420031781. HS 8481.80.
| Brand | Danfoss |
| Part number | 013G3362 |
| Type | RA-KE/KEW |
| Product group | Manifold Assemblies |
| Application | 1-pipe system |
| Valve type | RA-KE with elbow |
| RLV (return lockshield) type | no RLV |
| Design | Straight |
| Connection size (manifold side) | G 1/2 |
| Connection size (radiator side) | R 1/2 |
| Contents of set | Valve |
| Kvs value | 2.5 m³/h |
| Differential pressure (max) | 0.6 bar |
| Flow temperature (max) | 120 °C |
| Working pressure (max) | 10 bar |
| Test pressure | 16 bar |
| Feature description | RA-KE Valve body |
| REACH candidate-list substances | Lead (CAS no. 7439-92-1) |
| EU RoHS compliance | Yes with exemptions |
| Net weight | 0.374 Kilogram |
| Gross weight | 0.374 Kilogram |
| Packed volume | 0.343 Liter |
| EAN | 5702420031781 |
| HS code | 8481.80 (taps, cocks, valves for pipes, tanks, vats or the like) |
| Material | Body brass |
| Pressure rating | 10 bar max working (test 16 bar) |
| Temperature range | up to 120 °C (flow) |
| MOQ | 1 |
Single-pipe radiator manifold valve body for the Danfoss RA-K/RA-KE system, straight pattern, G 1/2 manifold connection / R 1/2 radiator connection. Accepts a Danfoss RA-series thermostatic sensor or thermal/electric actuator on the valve clamp ring. Confirm the system type (1-pipe system), connection pattern (Straight) and variant (RA-KE/KEW) against the installation before ordering.