Danfoss MP54 oil differential pressure switch, fixed differential, automatic reset, 1/4 in flare

Danfoss · Sensors & Instrumentation · Pressure Switches · Denmark · danfoss.com
Part Number
060B029791  ·  HS 9026.20
Danfoss MP54 oil differential pressure switch, fixed differential, automatic reset, 1/4 in flare

Danfoss MP54 oil differential pressure switch, genuine OEM code number 060B029791. Protects a refrigeration or air-conditioning compressor against loss of lubricating oil pressure by monitoring the differential between oil-pump pressure and crankcase (suction) pressure and cutting out when it falls below the set value. Fixed differential; automatic reset. SPDT contact system, 1/4 in flare (DIN 8906) pressure connection, screwed cable entry (Pg 13.5), IP20 enclosure. Max. working pressure 17 bar. Suitable for HCFC and non-flammable HFC refrigerants. EAN 5702424499631.

Technical Specifications

BrandDanfoss
Part number (code number)060B029791
TypeMP54 oil differential pressure switch (lubrication safety control)
CategorySensors & Instrumentation — Pressure Switches
Functioncuts out on falling oil pressure (differential of oil-pump pressure over crankcase pressure)
Differential settingfixed, contact differential 0.2 bar
Resetautomatic
Time-delay relaynone (automatic reset version)
Contact systemSPDT
Contact ratingAC15=0.1 A, 250 V DC13=12 W, 125 V
Pressure connection1/4 in flare (DIN 8906)
Max. working pressure17 bar (245 psig)
Max. test pressure22 bar
Operating range
LP side-1 bar to 12 bar
Electrical connectionScrewed cable entry Pg 13.5
Enclosure ratingIP20
Ambient temperature-40 °C to 60 °C
Refrigerant compatibilityHCFC and non-flammable HFC (e.g. R22, R134a, R404A, R407C, R448A, R449A, R450A, R513A)
PackingMulti pack (21 pc)
EAN5702424499631
HS code9026.20

Properties

MaterialBellows-type differential pressure element; IP20 enclosure
Pressure ratingmax. working pressure 17 bar (245 psig); test 22 bar
Temperature range-40 °C to 60 °C ambient
IP ratingIP20
Standard size1/4 in flare (DIN 8906)
Thread standard1/4 in flare (DIN 8906)
MOQ1

Compatibility

MP54 lube-oil protection control for reciprocating and scroll refrigeration/AC compressors. MP54 has a fixed differential (no setting disc). The automatic-reset variant is distinct from the other MP time-delay/reset options — verify the required time delay and reset (manual vs automatic) for the compressor.

Standards

Approvals