Danfoss MP54 oil differential pressure switch, genuine OEM code number 060B029791. Protects a refrigeration or air-conditioning compressor against loss of lubricating oil pressure by monitoring the differential between oil-pump pressure and crankcase (suction) pressure and cutting out when it falls below the set value. Fixed differential; automatic reset. SPDT contact system, 1/4 in flare (DIN 8906) pressure connection, screwed cable entry (Pg 13.5), IP20 enclosure. Max. working pressure 17 bar. Suitable for HCFC and non-flammable HFC refrigerants. EAN 5702424499631.
| Brand | Danfoss |
| Part number (code number) | 060B029791 |
| Type | MP54 oil differential pressure switch (lubrication safety control) |
| Category | Sensors & Instrumentation — Pressure Switches |
| Function | cuts out on falling oil pressure (differential of oil-pump pressure over crankcase pressure) |
| Differential setting | fixed, contact differential 0.2 bar |
| Reset | automatic |
| Time-delay relay | none (automatic reset version) |
| Contact system | SPDT |
| Contact rating | AC15=0.1 A, 250 V DC13=12 W, 125 V |
| Pressure connection | 1/4 in flare (DIN 8906) |
| Max. working pressure | 17 bar (245 psig) |
| Max. test pressure | 22 bar |
| Operating range | |
| LP side | -1 bar to 12 bar |
| Electrical connection | Screwed cable entry Pg 13.5 |
| Enclosure rating | IP20 |
| Ambient temperature | -40 °C to 60 °C |
| Refrigerant compatibility | HCFC and non-flammable HFC (e.g. R22, R134a, R404A, R407C, R448A, R449A, R450A, R513A) |
| Packing | Multi pack (21 pc) |
| EAN | 5702424499631 |
| HS code | 9026.20 |
| Material | Bellows-type differential pressure element; IP20 enclosure |
| Pressure rating | max. working pressure 17 bar (245 psig); test 22 bar |
| Temperature range | -40 °C to 60 °C ambient |
| IP rating | IP20 |
| Standard size | 1/4 in flare (DIN 8906) |
| Thread standard | 1/4 in flare (DIN 8906) |
| MOQ | 1 |
MP54 lube-oil protection control for reciprocating and scroll refrigeration/AC compressors. MP54 has a fixed differential (no setting disc). The automatic-reset variant is distinct from the other MP time-delay/reset options — verify the required time delay and reset (manual vs automatic) for the compressor.