Danfoss MBT 9110 temperature transmitter, Pt 100, -50 to +200 C (-58 to +392 F), 4-20 mA output (code 084Z6000)

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
084Z6000  ·  HS 9025.19
Danfoss MBT 9110 temperature transmitter, Pt 100, -50 to +200 C (-58 to +392 F), 4-20 mA output (code 084Z6000)

Danfoss MBT 9110 temperature transmitter, code 084Z6000 (type designation MBT 9110-000B-A420). Two-wire loop-powered head/box transmitter converting a Pt 100 signal into a 4-20 mA output proportional to the factory-set measuring range -50 to +200 C (-58 to +392 F), for temperature monitoring in general industry and marine installations. Pt 100 platinum input (100 ohm at 0 C) per EN 60751. Supply voltage 8-35 V DC; standard high-lid enclosure, IP54. CE marked.

Technical Specifications

TypeMBT 9110 (temperature transmitter, head/box)
Type designationMBT 9110-000B-A420
Code number084Z6000
Sensor inputPt 100 platinum resistance (100 ohm at 0 C) per EN 60751
Measuring range-50 to +200 C (-58 to +392 F)
Output signal4-20 mA (2-wire, loop-powered)
Supply voltage8-35 V DC
EnclosureStandard, high lid
Enclosure ratingIP54
ApprovalsCE
EAN5702423123414
Product groupSensors
Ambient temperature max.85 °C
Temperature range-200 °C to 850 °C
CE markYes
REACH candidate-list substancesLead (CAS no. 7439-92-1)
Net weight0.117 kg
EEE category5 small equipment (any external dimension < 50 cm)
Electrical connectionOutput 2 wire
Electrical connection size2 terminals
Enclosure rating IPIP54
In scope of WEEEYes
Insertion typeFixed
Sensor elem. resistance100 Ohm
Sensor element1 pc
Sensor element typePt
Supply voltage [V] DC8.00 V to 35.00 V
Transmitter setting range-50 °C to 200 °C
Transmitter typeStandard, high lid
EU RoHS complianceYes with exemptions

Properties

Temperature range-50 to +200 C (-58 to +392 F)
IP ratingIP54
MOQ1