cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss MBT 5113 temperature transmitter, Type K thermocouple, 100 mm insertion, G 1/2, 4-20 mA output (code 084Z2317)

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
084Z2317  ·  HS 9025.19
Danfoss MBT 5113 temperature transmitter, Type K thermocouple, 100 mm insertion, G 1/2, 4-20 mA output (code 084Z2317)

Danfoss MBT 5113 high-temperature transmitter, code 084Z2317 (type designation MBT 5113-B002-100-00-H180). Integrated Type K thermocouple (NiCr-Ni) and 2-wire loop-powered transmitter delivering a 4-20 mA output, for flue gas, engine exhaust and high-temperature process measurement. Thermocouple to Class 2 per EN 60584-2. Insertion length 100 mm; G 1/2 male (ANSI/ASME B1.20.1) process connection; AISI 316 Ti protection tube, 14-24 mm diameter. Measuring range -50 to +800 C (-58 to +1472 F); Type B connection head, Pg 16; IP65 enclosure per IEC 60529. CE marked.

Technical Specifications

TypeMBT 5113 (high-temperature thermocouple transmitter)
Type designationMBT 5113-B002-100-00-H180
Code number084Z2317
Sensor elementType K thermocouple (NiCr-Ni), Class 2 per EN 60584-2
Insertion length100 mm
Process connectionG 1/2 male (ANSI/ASME B1.20.1)
Protection tubeAISI 316 Ti stainless steel, 14-24 mm diameter
Measuring range-50 to +800 C (-58 to +1472 F)
Output signal4-20 mA (2-wire, loop-powered)
Electrical connectionType B connection head, Pg 16
Enclosure ratingIP65 per IEC 60529
Packing quantity8 pc
Net weight0.566 kg
ApprovalsCE
EAN5702428895705
Product groupSensors
Ambient temperature max. [°C]85 °C
Ambient temperature max. [°F]185 °F
ApprovalCE
CE markYes
China RoHS complianceOut of scope
Connection materialAISI 316 Ti
Connection typeG
EEE category5 small equipment (any external dimension < 50 cm)
Electrical connection sizePg 16
Enclosure rating IPIP65
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Extension length [in]3.94 in
Extension length [mm]100 mm
In scope of WEEEYes
Insertion length [in]3.94 in
Insertion length [mm]100 mm
Insertion typeFixed
Number of terminals [pcs]2 pc
Output signal [mA] [max]20 mA
Output signal [mA] [min]4 mA
Process connection Male/FemaleMale
Process connection materialAISI 316 Ti
Process connection size1/2
Process connection standardANSI/ASME B1.20.1
Process connection typeG
Protection tube diameter [in] [max]0.945 in
Protection tube diameter [in] [min]0.551 in
Protection tube diameter [mm] [max]24 mm
Protection tube diameter [mm] [min]14 mm
Protection tube materialAISI 316 TI
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Sensor element standardEN 60584-2
Sensor element toleranceClass 2
Sensor InsertExchangeable
Supply voltage [V] DC [max]35 V
Supply voltage [V] DC [min]8 V
Temperature range [°C] [max]800 °C
Temperature range [°C] [min]-50 °C
Temperature range [°F] [max]1472 °F
Temperature range [°F] [min]-58 °F
Thermocouple1 X NiCr-Ni, Type K
Thermocouple design std.EN 61515
Thermocouple toleranceEN 60584-2 Class 2
Transmitter setting range [°C] [max]800 °C
Transmitter setting range [°C] [min]0 °C
Transmitter setting range [°F] [max]1472 °F
Transmitter setting range [°F] [min]32 °F
Transmitter typeGalv. isolated
Wires [pcs]2 pc

Properties

MaterialAISI 316 Ti stainless steel
Temperature range-50 to +800 C (-58 to +1472 F)
IP ratingIP65
Standard size100 mm insertion
Thread standardANSI/ASME B1.20.1
MOQ1

Compatibility

MBT 5113 thermocouple transmitter (4-20 mA). Confirm the -50 to +800 C range suits the process, the G 1/2 thread and thermowell bore fit the 14-24 mm tube, and a loop supply is available. Type K element.

Standards

Approvals

Attached Documents