Danfoss MBT 120 sensor pocket (thermowell), code 084Z2442 (type designation MBT 120-630-200-C). Protects an inserted MBT temperature sensor from process pressure and flow and allows removal of the sensor without opening the process. AISI 316 Ti protection tube, 11 mm diameter; insertion length 200 mm; G 1/2 male process connection (ISO 228-1-A). Service temperature -50 to +200 C (-58 to +392 F). Used with MBT 3560, MBT 5560. CE marked.
| Type | MBT 120 sensor pocket (thermowell) |
| Type designation | MBT 120-630-200-C |
| Code number | 084Z2442 |
| Insertion length | 200 mm |
| Process connection | G 1/2 (ISO 228-1-A) |
| Protection tube | AISI 316 Ti, 11 mm diameter |
| Service temperature | -50 to +200 C (-58 to +392 F) |
| Used for | MBT 3560, MBT 5560 |
| Packing quantity | 20 pc |
| Net weight | 0.132 kg |
| Approvals | CE |
| EAN | 5702428973366 |
| Product group | Accessories, sensors |
| Approval | CE |
| CE mark | Yes |
| China RoHS compliance | Out of scope |
| Connection material | AISI 316 Ti |
| Connection standard | ISO 228 |
| Connection type | G |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| EU RoHS compliance | Yes |
| In scope of WEEE | Yes |
| Insertion length [in] | 7.9 in |
| Insertion length [mm] | 200 mm |
| Internal connection size | 1/2 |
| Internal connection type | G |
| Process connection Male/Female | Male |
| Process connection material | AISI 316 Ti |
| Process connection size | 1/2 |
| Process connection standard | ISO 228-1-A |
| Process connection type | G |
| Protection tube diameter [in] | 0.433 in |
| Protection tube diameter [mm] | 11 mm |
| Protection tube material | AISI 316 TI |
| REACH Candidate List substances | No |
| Temperature range [°C] [max] | 200 °C |
| Temperature range [°C] [min] | -50 °C |
| Temperature range [°F] [max] | 392 °F |
| Temperature range [°F] [min] | -58 °F |
| UL mark | No |
| Used for product | MBT 3560, MBT 5560 |
| Material | AISI 316 Ti |
| Temperature range | -50 to +200 C (-58 to +392 F) |
| Standard size | 200 mm insertion |
| Thread standard | ISO 228-1-A |
| MOQ | 1 |
MBT 120 thermowell. Confirm insertion length (200 mm), process thread (G 1/2) and bore suit the host sensor (MBT 3560, MBT 5560) and mounting boss.