Danfoss KPI35 pressure switch, code 060-130366. Factory setting 4.8 bar with a fixed 1.4 bar differential, automatic reset, SPDT snap-action contact. G 1/4 in (ISO 228-1, male) pressure connection, IP55 enclosure, max working pressure 18 bar. A preset, sealed IP55 KPI35 for fixed-setpoint low-pressure control in refrigeration/AC. RINA marine approval plus CE, UL, CCC, EAC. Bellows pressure element.
| Type | KPI35 pressure switch |
| Code number | 060-130366 |
| Setting | factory-set 4.8 bar (70 psig) |
| Differential | 1.4 bar (fixed) |
| Reset | automatic |
| Contact system | SPDT |
| Connection | G 1/4 in (ISO 228-1, male) |
| Max working pressure | 18 bar |
| Enclosure | IP55 |
| Approvals | CE, UL, CCC, EAC, RINA |
| EAN | 5702423215430 |
| Product group | Switches and thermostats |
| Max. test pressure | 261.0 psig |
| Max. test pressure Pe | 18.0 bar |
| Ambient temperature range | -40 °C to 65 °C |
| UL approval file name | E31024 |
| UL mark | Yes |
| CE mark | Yes |
| REACH candidate-list substances | Lead (CAS no. 7439-92-1); Cadmium oxide (CAS no.1306-19-0) |
| Net weight | 0.423 kg |
| Alarm Signal | Rising |
| Amb | |
| Temp | |
| Note | 80 °C/176 °F for max 120 min |
| Contact function | SPDT |
| Contact rating | AC15=4 A, 440 V; AC1=10 A, 440 V; AC3=6 A, 440 V; DC13=12 W, 220 V; LR=36 A, 240 V; LR=48 A, 120 V |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| Electrical connection | Rubber cable gland |
| Electrical connection size | 6-14 mm |
| EN 60947 electrical properties | Insulation: 400V; Pollution degree: 3; Rated impulse voltage: 4 kV; Short circuit prot, fuse: 16A |
| EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2; Flex, no ferrules: 0.7-2.5 mm2; Solid/stranded: 0.75-2.5 mm2 |
| Enclosure rating IP | IP55 |
| Factory setting | 0.480 MPa, 70.0 psig |
| In scope of WEEE | Yes |
| Pressure connection size | 1/4 |
| Pressure connection standard | ISO 228-1 |
| Pressure connection type | G |
| Pressure Male/Female | Male |
| Pressure sensing element | Bellows |
| Reset function | Auto |
| EU RoHS compliance | Out of scope |
| Material | Steel/zinc-plated housing; bellows pressure element |
| Pressure rating | max working pressure 18 bar |
| Temperature range | -40 to +65 °C |
| IP rating | IP55 |
| Thread standard | G 1/4 in (ISO 228-1, male) |
| MOQ | 1 |
Fixed-setpoint (4.8 bar) low-pressure control; automatic reset. Preset, sealed IP55 variant of KPI35.