Danfoss KP7ABS dual high-pressure safety switch for refrigeration and air-conditioning plants. Both sides adjustable 8–32 bar with a fixed 4 bar differential, contact system 2 × SPST-NC, manual (max) reset on both sides. Maximum working pressure 35 bar, burst pressure 140 bar, bellows sensing element, pressure connection 12 × 1.5 ISO 8434-1 male for 6 mm cutting-ring tube, rubber cable gland 6–14 mm, enclosure IP30, ambient −25 to 65 °C. Approved to CE, PED, LVD, UL873 and marine classification DNV, RINA and RMRS. Suitable for common HFC/HFO refrigerants and R717; not for liquid-line duty.
| Type | KP7ABS |
| Regulation range (both sides) | 8–32 bar |
| Differential (fixed, both sides) | 4 bar |
| Contact system | 2 × SPST-NC |
| Reset | Manual (max), both sides |
| Max working pressure | 35 bar |
| Burst pressure | 140 bar |
| Pressure connection | 12 × 1.5 ISO 8434-1 male (6 mm cutting ring) |
| Electrical connection | Rubber cable gland 6–14 mm |
| Enclosure | IP30 |
| Ambient temperature | −25 to 65 °C |
| Approvals | CE, PED, LVD, UL873, DNV, RINA, RMRS, EAC, CCC |
| Net weight | 0.65 kg |
| EAN | 5702428187114 |
| HS code | 9032.20 |
| Manufacturer part number (MPN) | 060-508866 |
| Temperature range | −25 to 65 °C |
| IP rating | IP30 |
| Weight | 0.65 kg |
| MOQ | 1 |
Dual safety pressure switch of the KP7 programme. Confirm the required reset variant and pressure connection against the plant specification before ordering.