Danfoss KP77 thermostat, code 060L600066. Regulating range 20 to 60 °C (68 to 140 °F) via rigid (direct-mounted) sensor. Differential 5 K (fixed), adjustable; automatic reset; SPDT snap-action contact. Enclosure IP30; ambient -40 to +70 °C; maximum sensor temperature 130 °C (266 °F). For temperature monitoring, control and limit protection of non-aggressive media. EAN 5702428014830.
| Type | KP77 thermostat |
| Code number | 060L600066 |
| Setting (regulating) range | 20 to 60 °C (68 to 140 °F) |
| Differential | 5 K (fixed) (adjustable, min. range) |
| Reset | Automatic |
| Contact system | SPDT |
| Sensor | remote bulb |
| Sensor size | Ø9.5 × 85 mm |
| Capillary tube length | 2000 mm |
| Max. sensor temperature | 130 °C (266 °F) |
| Enclosure | IP30 |
| Ambient temperature | -40 to +70 °C |
| Electrical connection | Rubber cable gland (6–14 mm) |
| Connection for pocket | M 18 × 1.5 |
| Contact rating | AC15=10 A/400 V; AC1=16 A/400 V; AC3=16 A/400 V; DC13=12 W/220 V; LR=112 A/400 V |
| Approvals | CE, EAC, CCC, DNV, BV, GL, LR, RINA, RMRS, LVD, CMIM, UL |
| EAN | 5702428014830 |
| Net weight | 0.349 Kilogram |
| Product group | Switches and thermostats |
| Alarm Signal | Rising |
| Amb | |
| Temp | |
| Note | 80 °C/176 °F for max 120 min |
| Ambient temperature range [°C] [max] | 70 °C |
| Ambient temperature range [°C] [min] | -40 °C |
| Ambient temperature range [°F] [max] | 158 °F |
| Ambient temperature range [°F] [min] | -40 °F |
| Approval | BV |
| Cap. tube length fraction [in] | 78 3/4 in |
| Capillary tube length [mm] | 2000 mm |
| CE mark | Yes |
| Charge type | Adsorption |
| China RoHS compliance | Yes |
| Contact function | SPDT |
| Differential (FS) [K] | 5 K |
| Differential type | Fixed (max. value) |
| Electrical connection size | 6-14 mm |
| Electrical spec. standard | EN 60947-5 |
| EN 60947 electrical properties | Insulation: 400V |
| EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2 |
| Enclosure rating IP | IP30 |
| Enclosure rating Nema (~) | 1 |
| EU RoHS compliance | Yes |
| Factory setting (FS) [°C] | 35 °C |
| Factory setting type | Dedicated |
| Max. sensor temperature [°C] | 130 °C |
| Max. sensor temperature [°F] | 266 °F |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Reset function | Auto |
| Sensor size (Ø x L) [in] | 3/8 x 3 3/8 in |
| Sensor size (Ø x L) [mm] | 9.5 x 85 mm |
| Sensor type | Remote bulb |
| Temperature range [°C] [max] | 60 °C |
| Temperature range [°C] [min] | 20 °C |
| Temperature range [°F] [max] | 140 °F |
| Temperature range [°F] [min] | 68 °F |
| UL approval file name | E31024 |
| UL mark | Yes |
| Material | remote bulb sensor with enamelled die-cast aluminium housing and steel capillary |
| Temperature range | -40 to +70 °C |
| IP rating | IP30 |
| MOQ | 1 |
KP77 temperature switch for HVAC-R temperature regulation and limit/overheat protection. Factory set 35 °C. Verify regulating range (20 to 60 °C) and differential against the set point before ordering.