cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss KP75 thermostat, 0 to 40 °C, automatic, SPDT gold-plated, room sensor 25 x 78 mm

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L117166  ·  HS 9032.10
Danfoss KP75 thermostat, 0 to 40 °C, automatic, SPDT gold-plated, room sensor 25 x 78 mm

Danfoss KP75 thermostat, code 060L117166. Sensor (regulating) range 0 to 40 °C (32 to 104 °F) via room sensor 25 x 78 mm. Differential 3 K (max range setting); 4 to 10 K (min range setting); automatic; SPDT gold-plated (low-current) snap-action contact. Enclosure IP30, ambient -40 to +65 °C (80 °C for max 120 min); maximum sensor temperature 80 °C. Carries marine type approval (DNV/BV/GL/LR/RINA/RMRS). For temperature monitoring, control and frost/overheat protection of non-aggressive media. EAN 5702423148769.

Technical Specifications

TypeKP75 thermostat
Code number060L117166
Sensor (regulating) range0 to 40 °C (32 to 104 °F)
Differential3 K (max range setting); 4 to 10 K (min range setting)
ResetAutomatic
Contact systemSPDT gold-plated (low-current)
Contact ratingAC15 4 A 400 V; AC1 10 A 400 V; AC3 6 A 400 V (gold contacts)
Sensorroom sensor 25 x 78 mm
Maximum sensor temperature80 °C
EnclosureIP30
Ambient temperature-40 to +65 °C (80 °C for max 120 min)
Electrical connectionrubber cable gland 6-14 mm
ApprovalsCE, EAC, CCC, UL, CSA, DNV, BV, GL, LR, RINA, RMRS, LVD, CMIM
EAN5702423148769
Net weight0.356 Kilogram
Product groupSwitches and thermostats
Amb
Temp
Note80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max]65 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]150 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalBV
CE markYes
Charge typeAdsorption
China RoHS complianceYes
Contact functionSPDT gold
Diff. @ Max. range setting [K]3 K
Diff. @ Max. range setting[°C]3 °C
Diff. @ Min. range setting [K] [max]10 K
Diff. @ Min. range setting [K] [min]4 K
Diff. @ Min. range setting[°C] [max]10 °C
Diff. @ Min. range setting[°C] [min]4 °C
Differential typeAdjustable
Electrical connection size6-14 mm
Electrical spec. standardEN 60947-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
EU RoHS complianceYes
Max. sensor temperature [°C]80 °C
Max. sensor temperature [°F]176 °F
Parts includedScrews
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionAuto
Sensor size (Ø x L) [in]1 x 3 in
Sensor size (Ø x L) [mm]25 x 78 mm
Sensor typeRoom sensor
Temperature range [°C] [max]40 °C
Temperature range [°C] [min]0 °C
Temperature range [°F] [max]104 °F
Temperature range [°F] [min]32 °F
UL approval file nameE31024
UL markYes

Properties

MaterialRoom sensor with steel housing; gold-plated contacts
Temperature range-40 to +65 °C (80 °C for max 120 min)
IP ratingIP30
MOQ1

Compatibility

KP75 temperature switch for HVAC-R temperature regulation and frost/overheat protection. SPDT contact wired NO or NC. Verify regulating range (0 to 40 °C) and differential against the set point before ordering.

Standards

Approvals

Attached Documents