cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss KP71 thermostat, -4 to 21 °C, automatic reset, remote bulb

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L201066  ·  HS 9032.10
Danfoss KP71 thermostat, -4 to 21 °C, automatic reset, remote bulb

Danfoss KP71 thermostat, code 060L201066. Sensor (regulating) range -4 to 21 °C (25 to 70 °F) via remote bulb, 2030 mm capillary tube. Differential 2.2 to 9 K (min range); 3 to 10 K (max range); automatic; SPDT (single-pole double-throw) snap-action contact. Enclosure IP30; ambient -40 to +65 °C. Carries marine type approval (DNV/BV/GL/LR/RINA/RMRS). For temperature monitoring, control and limit protection of non-aggressive media. EAN 5702428016735.

Technical Specifications

TypeKP71 thermostat
Code number060L201066
Sensor (regulating) range-4 to 21 °C (25 to 70 °F)
Differential2.2 to 9 K (min range); 3 to 10 K (max range)
ResetAutomatic
Contact systemSPDT (single-pole double-throw)
Sensorremote bulb
Capillary tube length2030 mm
EnclosureIP30
Ambient temperature-40 to +65 °C
Electrical connectionrubber cable gland
ApprovalsCE, EAC, CCC, UL, CSA, DNV, BV, GL, LR, RINA, RMRS, LVD, CMIM
EAN5702428016735
Net weight0.416 Kilogram
Product groupSwitches and thermostats
Amb
Temp
Note80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max]65 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]150 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalBV
Cap. tube length fraction [in]80 in
Capillary tube length [mm]2030 mm
CE markYes
Charge typeAdsorption
China RoHS complianceYes
Contact functionSPDT
Contact rating120 V ac, 16 FLA, 96 LRA
Diff. @ Max. range setting [K] [max]9 K
Diff. @ Max. range setting [K] [min]2.2 K
Diff. @ Max. range setting[°C] [max]9 °C
Diff. @ Max. range setting[°C] [min]2.2 °C
Diff. @ Max. range setting[°F] [max]16 °F
Diff. @ Max. range setting[°F] [min]4 °F
Diff. @ Min. range setting [K] [max]10 K
Diff. @ Min. range setting [K] [min]3 K
Diff. @ Min. range setting[°C] [max]10 °C
Diff. @ Min. range setting[°C] [min]3 °C
Diff. @ Min. range setting[°F] [max]18 °F
Diff. @ Min. range setting[°F] [min]5.4 °F
Differential typeAdjustable
Electrical conn
Male/FemaleFemale
Electrical connection sizeNPSM 1/2 - 14
Electrical connection standardANSI/ASME B1.20.1
Electrical spec. standardEN 60947-4/-5
EN 60947 electrical propertiesInsulation: 400V
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
EU RoHS complianceYes
Max. sensor temperature [°C]80 °C
Max. sensor temperature [°F]176 °F
Parts includedScrews
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Reset functionAuto
Sensor size (Ø x L) [in]3/8 x 4 1/2 in
Sensor size (Ø x L) [mm]9.5 x 115 mm
Sensor typeRemote bulb
Temperature range [°C] [max]21 °C
Temperature range [°C] [min]-4 °C
Temperature range [°F] [max]70 °F
Temperature range [°F] [min]25 °F
UL approval file nameE31024
UL markYes

Properties

Materialremote bulb with steel housing
Temperature range-40 to +65 °C
IP ratingIP30
MOQ1

Compatibility

KP71 temperature switch for HVAC-R temperature regulation and limit/frost/overheat protection. Contact wired NO or NC. Verify regulating range (-4 to 21 °C) and differential against the set point before ordering.

Standards

Approvals

Attached Documents