Danfoss KP63 thermostat, -50 to 10 °C, automatic reset, SPDT, capillary sensor 2.5 x 500 mm

Danfoss · Sensors & Instrumentation · Temperature Sensors · Denmark · danfoss.com
Part Number
060L110766  ·  HS 9032.10
Danfoss KP63 thermostat, -50 to 10 °C, automatic reset, SPDT, capillary sensor 2.5 x 500 mm

Danfoss KP63 thermostat (code 060L110766). Sensor (regulating) range -50 to 10 °C with a capillary tube sensor 2.5 x 500 mm (Ø x L) and 2000 mm capillary tube. Adjustable differential 2.7 to 8 K at the maximum range setting; automatic reset; SPDT (single-pole double-throw) snap-action contact. Enclosure IP30, ambient -40 to +65 °C. Maximum sensor temperature 120 °C. For low-temperature monitoring and control of non-aggressive media.

Technical Specifications

TypeKP63 thermostat
Code number060L110766
Sensor (regulating) range-50 to 10 °C
Differential2.7 to 8 K (max range setting), adjustable
ResetAutomatic
Contact systemSPDT (single-pole double-throw)
Sensorcapillary tube sensor 2.5 x 500 mm (Ø x L)
Capillary tube length2000 mm
Maximum sensor temperature120 °C
EnclosureIP30
Ambient temperature-40 to +65 °C
Electrical connectionrubber cable gland 6-14 mm
Contact ratingAC15 10 A 400 V; AC1 16 A 400 V; AC3 16 A 400 V; DC13 12 W 220 V; LR 112 A 400 V
ApprovalsCE, EAC, CCC, UL (UL873), DNV, BV, GL, LR, RINA, RMRS, LVD
Product groupSwitches and thermostats
Max. sensor temperature120 °C
Temperature range-50 °C to 10 °C
UL approval file nameE31024
UL markYes
CE markYes
REACH candidate-list substancesLead (CAS no. 7439-92-1); Cadmium oxide (CAS no.1306-19-0)
Net weight0.366 kg
EAN5702428014540
Amb
Temp
Note80 °C/176 °F for max 120 min
Cap. tube length fraction78 3/4 in
Charge typeVapour
Contact functionSPDT
Diff. @ Max. range setting2.7 K to 8.0 K, 2.7 °C to 8.0 °C
Diff. @ Min. range setting10.0 K to 70.0 K, 10.0 °C to 70.0 °C
Differential typeAdjustable
Electrical connection size6-14 mm
Electrical spec. standardEN 60947-5
EN 60947 electrical propertiesInsulation: 400V; Pollution degree: 3; Rated impulse voltage: 4 kV; Short circuit prot, fuse: 16A
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2; Flex, no ferrules: 0.7-2.5 mm2; Solid/stranded: 0.75-2.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
Reset functionAuto
Sensor size (Ø x L)2.5 x 500 mm
Sensor typeCapillary tube sensor
EU RoHS complianceYes

Properties

MaterialCapillary tube sensor with steel housing
Temperature range-40 to +65 °C
IP ratingIP30
MOQ1

Compatibility

Low-temperature capillary-sensor cooling thermostat. SPDT contact wired NO or NC. Verify regulating range and differential against the set point before ordering.

Standards

Approvals

Attached Documents