cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss KP36 pressure switch, 1–10.5 bar, manual (max) reset, SPDT, G 1/2

Danfoss · Sensors & Instrumentation · Pressure Switches · Denmark · danfoss.com
Part Number
060-216066  ·  HS 9026.20
Danfoss KP36 pressure switch, 1–10.5 bar, manual (max) reset, SPDT, G 1/2

Danfoss KP36 single-pressure switch (code 060-216066) with manual maximum reset. Regulating range 1–10.5 bar, fixed differential 0.7 bar, SPDT snap-action contact. G 1/2 male connection per ISO 228-1, IP30 enclosure, ambient -40 to +65 °C. Max test pressure 22 bar. Manual reset version for high-pressure cut-out and safety limiting of non-aggressive liquids and gases.

Technical Specifications

TypeKP36 single-pressure switch, manual reset
Code number060-216066
Regulating range1–10.5 bar
Differential0.7 bar (fixed)
Max test pressure (Pe)22 bar
Resetmanual (max)
Contact systemSPDT (single-pole double-throw)
Contact loadAC-1 16 A/400 V; AC-15 10 A/400 V; DC-13 12 W/220 V
ConnectionG 1/2 male (ISO 228-1)
EnclosureIP30 (IP55 with enclosure 060-033066/062866)
Ambient temperature-40 to +65 °C (80 °C max 120 min)
Net weightapprox. 0.3 kg
Vibration0–1000 Hz, 4 g
Product groupSwitches and thermostats
Max. test pressure319.0 psig
Max. test pressure Pe22.0 bar
Max. working pressure17.0 bar
ApprovalCCC; CE; CMIM; EAC; LLC CDC EURO-TYSK; LVD; RINA; RMRS; RoHS China; c UL us UL353, CS C22.2; c UL us UL873, CS C22.2
UL approval file nameE31024; MH27572
UL approved refrigerantsR1234yf; R1234ze(E); R452B; R454A; R454C; R455A
UL markYes
CE markYes
REACH candidate-list substancesLead (CAS no. 7439-92-1); Cadmium oxide (CAS no.1306-19-0)
EAN5702428365352
Amb
Temp
Note80 °C/176 °F for max 120 min
Contact functionSPDT
Contact rating120Vac,16FLA,96LRA,3APilotDuty; 16 A resistive, single phase; 240 V AC, 8 FLA, 48 LRA; 240V dc,12W pilot duty(0.05 A); 8 A resistive, single phase
EEE category5 small equipment (any external dimension < 50 cm)
Electrical connectionRubber cable gland
Electrical connection size6-14 mm
EN 60947 electrical propertiesInsulation: 400V; Pollution degree: 3; Rated impulse voltage: 4 kV; Short circuit prot, fuse: 16A
EN 60947 wiring propertiesFlex, ferrules: 0.5-1.5 mm2; Flex, no ferrules: 0.7-2.5 mm2; Solid/stranded: 0.75-2.5 mm2
Enclosure rating IPIP30
Enclosure rating Nema (~)1
In scope of WEEEYes
Pressure connection size1/2
Pressure connection standardISO 228-1
Pressure connection typeG
Pressure Male/FemaleMale
Pressure sensing elementBellows

Properties

MaterialSteel/zinc-plated housing; bellows pressure element
Pressure ratingmax test 22 bar
Temperature range-40 to +65 °C (80 °C max 120 min)
IP ratingIP30 (IP55 with enclosure 060-033066/062866)
Thread standardISO 228-1 (G 1/2 male)
MOQ1

Compatibility

Manual-reset (max) version for high-pressure cut-out / safety limiting; the switch latches on trip and requires manual reset. SPDT contact. IP30 as supplied; IP55 with enclosure 060-033066/062866. Distinct code from the auto-reset KP36 (060-215966) — verify reset type before ordering.

Standards

Approvals

Attached Documents