Danfoss KP15 combined low/high (dual) pressure switch, code 060-128066. LP side -0.2 to 7.5 bar (differential 0.7 to 4 bar, automatic reset) and HP side 8 to 32 bar (differential 4 bar, manual maximum reset), common SPDT contact. 1/4 in DIN 8906 flare pressure connections with a rubber cable gland (6-14 mm) cable entry, IP30 enclosure, MWP 17 bar (LP) / 35 bar (HP). LP automatic control with latching HP safety cut-out; rubber-gland cable-entry variant. Marine class approvals BV, DNV, GL, LR, RINA, RMRS.
| Type | KP15 dual pressure switch |
| Code number | 060-128066 |
| LP range | -0.2 to 7.5 bar (differential 0.7 to 4 bar) |
| HP range | 8 to 32 bar (differential 4 bar) |
| Reset | LP automatic / HP manual maximum |
| Contact system | SPDT |
| Connection | 1/4 in DIN 8906 flare |
| Cable entry | rubber cable gland (6-14 mm) |
| Max working pressure | 17 bar (LP) / 35 bar (HP) |
| Enclosure | IP30 |
| Approvals | BV, DNV, GL, LR, RINA, RMRS |
| EAN | 5702428012096 |
| Net weight | 0.4 Kilogram |
| Product group | Switches and thermostats |
| Amb | |
| Temp | |
| Note | 80 °C/176 °F for max 120 min |
| Ambient temperature range [°C] [max] | 65 °C |
| Ambient temperature range [°C] [min] | -40 °C |
| Ambient temperature range [°F] [max] | 149 °F |
| Ambient temperature range [°F] [min] | -40 °F |
| Application note | Not applicable for liquid line |
| Approval | BV |
| CE mark | Yes |
| China RoHS compliance | Yes |
| Contact function | SPDT |
| Contact rating | AC15=10 A, 400 V |
| Differential left side [bar] [max] | 4 bar |
| Differential left side [bar] [min] | 0.7 bar |
| Differential left side [psi] [max] | 58 psi |
| Differential left side [psi] [min] | 10 psi |
| Differential right side [bar] | 4 bar |
| Differential right side [psi] | 58 psi |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| Electrical connection | Rubber cable gland |
| Electrical connection size | 6-14 mm |
| EN 60947 electrical properties | Insulation: 400V |
| EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2 |
| Enclosure rating IP | IP30 |
| Enclosure rating Nema (~) | 1 |
| EU RoHS compliance | Yes |
| In scope of WEEE | Yes |
| Lubricants compatibility | Oilfree applications |
| Max.test press.left side[bar] | 20 bar |
| Max.test press.right side[bar] | 35 bar |
| MWP left side [bar] Pe | 17 bar |
| MWP left side [psig] Pe | 245 psig |
| MWP right side [bar] Pe | 35 bar |
| MWP right side [psig] Pe | 510 psig |
| Oil free refrigerants | R134a |
| Pressure connection size | 1/4 |
| Pressure connection standard | DIN 8906 |
| Pressure connection type | Flare |
| Pressure Male/Female | Male |
| Pressure sensing element | Bellows |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Refrigerants | R113 |
| Regulation left side [bar]Pe [max] | 7.5 bar |
| Regulation left side [bar]Pe [min] | -0.2 bar |
| Regulation left side range Pe | 6 inHg - 108 psig |
| Regulation right side [bar]Pe [max] | 32 bar |
| Regulation right side [bar]Pe [min] | 8 bar |
| Regulation right side [psig]Pe [max] | 464 psig |
| Regulation right side [psig]Pe [min] | 116 psig |
| Reset function, left side | Auto |
| Reset function, right side | Manual Max |
| UL approval file name | E31024 |
| UL approved refrigerants | R113 |
| UL mark | Yes |
| Material | Steel/zinc-plated housing; bellows pressure element |
| Pressure rating | max working pressure 17 bar (LP) / 35 bar (HP) |
| Temperature range | -40 to +65 °C |
| IP rating | IP30 |
| Thread standard | 1/4 in DIN 8906 flare (rubber cable gland 6-14 mm) |
| MOQ | 1 |
LP automatic control + latching HP safety cut-out; rubber-gland (6-14 mm) cable-entry variant of KP15.