Danfoss KP15 dual (combined low- and high-) pressure switch, code 060-126566. LP regulating range -0.2 to 7.5 bar (differential 0.7-4 bar); HP regulating range 8 to 32 bar (differential 4 bar). Automatic reset on both sides. Contact system SPDT+SPST(NO) — a separate normally-open auxiliary contact in addition to the SPDT change-over. 1/4 in flare (male, DIN 8906) connection. Combines low-suction-pressure and high-discharge-pressure protection of a refrigeration or air-conditioning compressor in a single unit. Distinct from the SPDT-only KP15 060-124166 by its added SPST(NO) auxiliary contact.
| Type | KP15 dual (LP + HP) pressure switch |
| Code number | 060-126566 |
| LP regulating range | -0.2 to 7.5 bar (differential 0.7-4 bar) |
| HP regulating range | 8 to 32 bar (differential 4 bar) |
| Reset | automatic (both LP and HP) |
| Contact system | SPDT+SPST(NO) |
| Contact load | AC-1 16 A/400 V; AC-15 10 A/400 V; AC-3 16 A/400 V; DC-13 12 W/220 V; LR 112 A/400 V |
| Connection | 1/4 in flare (male, DIN 8906) |
| Pressure | max test 20 bar (LP) / 35 bar (HP) |
| Enclosure | IP44 |
| Ambient temperature | -40 to +65 °C |
| EAN | 5702422044659 |
| Approvals (per Danfoss store) | CE, UL (E31024), BV, DNV, GL, LR, RINA, EU RoHS |
| Net weight | 0.482 Kilogram |
| Product group | Switches and thermostats |
| Amb | |
| Temp | |
| Note | 80 °C/176 °F for max 120 min |
| Ambient temperature range [°C] [max] | 65 °C |
| Ambient temperature range [°C] [min] | -40 °C |
| Ambient temperature range [°F] [max] | 149 °F |
| Ambient temperature range [°F] [min] | -40 °F |
| Application note | Not applicable for liquid line |
| Approval | BV |
| CE mark | Yes |
| China RoHS compliance | Yes |
| Contact function | SPDT+SPST(NO) |
| Contact rating | AC15=10 A, 400 V |
| Differential left side [bar] [max] | 4 bar |
| Differential left side [bar] [min] | 0.7 bar |
| Differential left side [psi] [max] | 58 psi |
| Differential left side [psi] [min] | 10 psi |
| Differential right side [bar] | 4 bar |
| Differential right side [psi] | 58 psi |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| Electrical connection | Rubber cable gland |
| Electrical connection size | 6-14 mm |
| EN 60947 electrical properties | Insulation: 400V |
| EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2 |
| Enclosure rating IP | IP44 |
| Enclosure rating Nema (~) | 2 |
| EU RoHS compliance | Yes |
| In scope of WEEE | Yes |
| Lubricants compatibility | Oilfree applications |
| Max.test press.left side[bar] | 20 bar |
| Max.test press.right side[bar] | 35 bar |
| MWP left side [bar] Pe | 17 bar |
| MWP left side [psig] Pe | 245 psig |
| MWP right side [bar] Pe | 35 bar |
| MWP right side [psig] Pe | 510 psig |
| Oil free refrigerants | R134a |
| Other RoHS documentation | Saudi Arabia RoHS |
| Pressure connection size | 1/4 |
| Pressure connection standard | DIN 8906 |
| Pressure connection type | Flare |
| Pressure Male/Female | Male |
| Pressure sensing element | Bellows |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Refrigerants | R113 |
| Regulation left side [bar]Pe [max] | 7.5 bar |
| Regulation left side [bar]Pe [min] | -0.2 bar |
| Regulation left side range Pe | 6 inHg - 108 psig |
| Regulation right side [bar]Pe [max] | 32 bar |
| Regulation right side [bar]Pe [min] | 8 bar |
| Regulation right side [psig]Pe [max] | 464 psig |
| Regulation right side [psig]Pe [min] | 116 psig |
| Reset function, left side | Auto |
| Reset function, right side | Auto |
| UL approval file name | E31024 |
| UL approved refrigerants | R113 |
| UL mark | Yes |
| Material | Steel/zinc-plated housing; two bellows pressure elements |
| Pressure rating | max test 20 bar (LP) / 35 bar (HP) |
| Temperature range | -40 to +65 °C |
| IP rating | IP44 |
| Thread standard | 1/4 in flare (SAE 45°) connection |
| MOQ | 1 |
Refrigeration/AC combined LP + HP protection in a single switch; automatic reset on both sides. Carries an extra SPST(NO) auxiliary contact versus the SPDT-only KP15 060-124166. Verify LP and HP set points and contact arrangement before ordering.