cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Danfoss ICS1 65 pilot-operated servo valve, butt weld 2½ in (65 mm), EN 10220, steel, Kv 70 m³/h (code 027H6144)

Danfoss · HVAC & Refrigeration · Expansion Valves · Denmark · danfoss.com
Part Number
027H6144  ·  HS 8481.80
Danfoss ICS1 65 pilot-operated servo valve, butt weld 2½ in (65 mm), EN 10220, steel, Kv 70 m³/h (code 027H6144)

Danfoss ICS1 65 pilot-operated servo main valve (code 027H6144) for industrial refrigeration. Straightway steel body with butt-weld connections both ends, 2½ in / 65 mm to EN 10220; flow coefficient Kv 70 m³/h (Cv 81.2 gal/min). The ICS 1 main valve carries a single pilot function module on its top cover; opening configuration full open by external hot gas with a manual open spindle. Maximum working pressure 65 bar (943 psig); media temperature -60 to +120 °C (-76 to 248 °F). Suitable for R717 (ammonia), R744 (CO₂), HFC and hydrocarbon refrigerants. Specifications per Danfoss store code 027H6144.

Technical Specifications

TypeICS1 65 pilot-operated servo valve
Code number027H6144
Size65 mm (2½ in)
DirectionStraightway
Inlet/outlet connectionButt weld, steel, EN 10220
Inlet/outlet connection size2½ in / 65 mm
Kv value70 m³/h (Cv 81.2 gal/min)
Body materialSteel
Connection materialSteel
Surface coatingZn (TLP)
Valve operationPilot operated (single pilot function module on top cover)
Opening configurationFull open by external hot gas
Manual operationManual open spindle
Maximum working pressure65 bar (943 psig)
Media temperature range-60 to +120 °C (-76 to 248 °F)
RefrigerantsR717 (ammonia), R744 (CO₂), R134a, R404A, R410A and other listed refrigerants
PED categoryII
ApprovalsEAC, TÜV, UL
ComplianceEU RoHS, China RoHS
EAN5715162688670

Properties

MaterialSteel
Pressure rating65 bar
Temperature range-60 to +120 °C
Primary standardEN 10220
Standard size65 mm (2½ in)
MOQ1

Compatibility

Danfoss ICS 1 single-pilot servo main valve. Manual open spindle allows forced opening during service. Verify Kv, pilot configuration and refrigerant duty before ordering.

Standards

Approvals

Attached Documents