Danfoss FIA 50 function module (Top Complete), fits 50 mm (2 in) FIA 50 strainer body, 52 bar (code 148B5748)

Danfoss · HVAC & Refrigeration · Filters & Driers · Denmark · danfoss.com
Part Number
148B5748  ·  HS 8421.99
Danfoss FIA 50 function module (Top Complete), fits 50 mm (2 in) FIA 50 strainer body, 52 bar (code 148B5748)

Danfoss FIA 50 function module (also called Top Complete) for the SVL Flexline modular industrial-refrigeration valve platform, store code 148B5748. The function module is the complete internal strainer top assembly (cover, spindle/insert carrier and gaskets) that mounts on the matching FIA 50 valve housing; the replaceable strainer insert itself (FIA INS, 38/72/100/150/250/500 micron) is ordered separately. It is the field-serviceable repair/replacement assembly, not a complete valve and not a loose gasket, so the strainer function can be renewed without cutting the housing out of the line. For R717 (ammonia), R744 (CO2) and fluorinated refrigerants and their oils. Maximum working pressure 52 bar g (754 psig); media temperature -60 to 150 C (-76 to 302 F). net weight 0.8 kg, gross weight 0.96 kg. Specifications per Danfoss store code 148B5748.

Technical Specifications

TypeFIA 50 function module (Top Complete) — strainer top assembly
Code number148B5748
Fits bodyFIA 50 strainer housing (50 mm (2 in))
Functionstrainer top assembly (insert ordered separately)
Housing/valve size class50 mm (2 in)
Maximum working pressure52 bar g (754 psig)
Media temperature range-60 to 150 C (-76 to 302 F)
Applicable mediaR717 (ammonia), R744 (CO2), HFC/HCFC refrigerants and oils
Weightnet weight 0.8 kg, gross weight 0.96 kg
ApprovalsCE
EAN5702428491112
BrandSVL Flexline
Product groupStrainers
Type designationTop Complete
Max. working pressure52.0 bar
Temperature range-60 °C to 150 °C
RefrigerantsR113; R114; R1150; R1233zd(E); R1234yf; R1234ze(E); R125; R1270; R1336mzz(Z); R134a; R152a; R170; R22; R227ea; R23; R236fa; R245fa; R290; R32; R401A; R402A; R402B; R404A; R407A; R407B; R407C; R407F; R407H; R408A; R409A; R410A; R413A; R417A; R421A; R422A; R422B; R422D; R427A; R438A; R442A; R444B; R447A; R447B; R448A; R449A; R449B; R450A; R452A; R452B; R454A; R454B; R454C; R455A; R463A; R502; R503; R507A; R508B…
REACH candidate-list substancesNo
EU RoHS complianceYes
Net weight0.8 Kilogram
ApprovalCE
China RoHS complianceYes
Max. Working Pressure [bar]52 bar
Max. Working Pressure [psig]754 psig
Temperature range [°C] [max]150 °C
Temperature range [°C] [min]-60 °C
Temperature range [°F] [max]302 °F
Temperature range [°F] [min]-76 °F
Used for productFIA 50

Properties

MaterialSteel
Pressure rating52 bar
Temperature range-60 to 150 C
Standard size50 mm
MOQ1

Compatibility

Danfoss SVL Flexline FIA 50 function module. Mounts on the matching FIA 50 valve housing / SVL 50 multifunction valve body. Pair with a FIA INS strainer insert in the required micron rating (38/72/100/150/250/500). Function modules are size-specific — confirm the housing nominal size (50 mm (2 in)) before ordering. Shares the SVL Flexline platform with SVA-S/SVA-L shut-off, REG regulating and the other check/strainer components of the same size.

Standards

Approvals