cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss EVRF solenoid valve, — flange, steel body, 28 bar, Capacity regulator / unloading valve (code 032F6250)

Danfoss · HVAC & Refrigeration · Solenoid Valves · Denmark · danfoss.com
Part Number
032F6250  ·  HS 8481.80
Danfoss EVRF solenoid valve, — flange, steel body, 28 bar, Capacity regulator / unloading valve (code 032F6250)

Danfoss EVRF solenoid valve for industrial and commercial refrigeration, store code 032F6250. Capacity regulator / unloading valve valve, solenoid-operated, with — flange connections. Maximum working pressure 28 bar (400 psig); media temperature range -40 to 105 °C. Body material: Steel body. Suitable for R134a, R22/R407C, R23, R404A/R507A, R407A/F, R410A, R448A, R449A, R450A, R452A. EVRF unloader flange valve — solenoid-operated capacity regulator (compressor unloading valve) mounted on the compressor flange. Ambient -40 to 55 °C. Weight: net 0.482 kg, gross 0.52 kg. Specifications per Danfoss store code 032F6250.

Technical Specifications

TypeEVRF solenoid valve
Code number032F6250
Connection— flange
FunctionCapacity regulator / unloading valve
Valve operationSolenoid-operated
Maximum working pressure28 bar (400 psig)
Media temperature range-40 to 105 °C
Body materialSteel body
Applicable refrigerantsR134a, R22/R407C, R23, R404A/R507A, R407A/F, R410A, R448A, R449A, R450A, R452A
Weightnet 0.482 kg, gross 0.52 kg
Coilordered separately
ApprovalsEAC
EAN5702422170563
Net weight0.482 Kilogram
Product groupSolenoid valves
Actuator system [mm]13.5 mm
Ambient temperature-40 - 55 °C
Ambient temperature range [°F] [max]131 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalEAC
China RoHS complianceYes
DirectionNone
EU RoHS complianceYes
Inlet connection typeFlange
Lubricants compatibilityAB
Manual operation optionNo
Max. Working Pressure [bar]28 bar
Max. Working Pressure [psig]400 psig
MaxOPD[bar] 10W AC18 bar
Medium temperature range [°C] [max]105 °C
Medium temperature range [°C] [min]-40 °C
Medium temperature range [°F] [max]221 °F
Medium temperature range [°F] [min]-40 °F
Outlet connection typeFlange
REACH Candidate List substancesLead (CAS no. 7439-92-1)
RefrigerantsR134a
Type designationCapacity Regulator

Properties

MaterialSteel body
Pressure rating28 bar
Temperature range-40 to 105 °C
Primary standardFlange
Standard size—
MOQ1

Compatibility

Danfoss EVRF refrigeration solenoid valve. Coil is ordered separately — match coil voltage/frequency and connector to the installation. Refrigerant and pressure compatibility per the Danfoss data sheet; verify against your system specification before ordering.

Approvals

Attached Documents