cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-09
sales@cballast.com
cballast.com

Danfoss EVMP normally-closed solenoid pilot valve, servo-piston, 2.4 mm orifice, for ICS servo-operated main valves (code 027B1123)

Danfoss · HVAC & Refrigeration · Pilot Valves · Denmark · danfoss.com
Part Number
027B1123  ·  HS 8481.80
Danfoss EVMP normally-closed solenoid pilot valve, servo-piston, 2.4 mm orifice, for ICS servo-operated main valves (code 027B1123)

Danfoss EVMP normally-closed (NC) solenoid pilot valve for the ICV Flexline / ICS servo-operated main-valve range, code 027B1123. Fitted in the pilot channel of an ICS main valve, the EVMP opens or closes the pilot flow electrically, giving the main valve an on/off (stop) function. This is the normally-closed version: the pilot is closed when de-energised. Servo-piston operated with a 2.4 mm orifice and a 13.5 mm actuator system; steel body with threaded inlet. Flow coefficient Kv 0.251 m3/h (Cv 0.29). Maximum working pressure 28 bar (406 psig). Medium temperature -50 to 60 C (-58 to 140 F); ambient -50 to 50 C. Coil is ordered separately. Supplied as a 20-piece multipack. For HCFC, HFC, R717 (ammonia) and R744 (CO2) systems.

Technical Specifications

TypeEVMP (solenoid pilot valve, normally closed)
Code number027B1123
SeriesCVP / CVPP / CVC / CVE / EVM / CVH pilot valves
FunctionSolenoid on/off pilot — Normally Closed (NC)
Valve operationServo-piston
Pressure range Pe28 bar
Orifice size2.4 mm
Actuator system13.5 mm
Kv value0.251 m3/h
Cv value0.29 gal/min
Maximum working pressure28 bar (406 psig)
Medium temperature range-50 to 60 C (-58 to 140 F)
Ambient temperature range-50 to 50 C
Inlet connectionThread
Body materialSteel
CoilOrdered separately (not included)
Manual operationNo
Net weight0.227 kg
Gross weight0.241 kg
ApprovalsEAC (LLC CDC TYSK)
EAN5702422133339

Properties

MaterialSteel
Pressure rating28 bar
Temperature range-50 to 60 C
MOQ1

Compatibility

Solenoid pilot for Danfoss ICS servo-operated main valves; gives the main valve an electrical stop function. This is the normally-closed (NC) version — closed when de-energised; the normally-open counterpart is EVM (027B1132). A coil (clip-on) must be ordered separately and matched to the supply voltage. Confirm the ICS valve size and pilot arrangement before ordering.

Approvals

Attached Documents