Danfoss ECL Comfort 310 Regulator - 230V AC, ECL 310

Danfoss · HVAC & Refrigeration · Thermostats & Controls · Denmark · danfoss.com
Part Number
087H3040  ·  HS 9032.89
Danfoss ECL Comfort 310 Regulator - 230V AC, ECL 310

Danfoss ECL Comfort 310 Regulator. Weather compensation system (Plumbing / Heat / Valves for heating and cooling systems). Principal data: supply voltage 230 V AC, fits with ECL 310. Supplied under manufacturer part number 087H3040, EAN 5710104013244, HS code 9032.89, country of origin China.

Technical Specifications

Product typeWeather compensation system
Product groupHeat
Supply voltage230 V AC
Fits withECL 310
Leakage classIP 41
Ambient temperature min0 °C
Ambient temperature max55 °C
REACH SVHC substance above 0.1%Lead
Sales unitPack, Plt.
Carbon footprint (EPD)5.0343 kg CO2e per pcs
Country of originChina
Customs tariff code (EU CN)90328900
HS code9032.89
Manufacturer part number087H3040
VVS number460944310
EAN5710104013244
Net weight0.476 Kilogram
TypeECL Comfort 310
Actuator output load [VA]15 VA
Ambient humidity [% RH] [Max]65 %
Ambient temperature [°C] [max]55 °C
Ambient temperature [°C] [min]0 °C
Application sourceBy ECL application key
ApprovalCE
Approval standardEMC-Directive: 2004/108/EC
CE markYes
China RoHS complianceOut of scope
CommunicationsECL 485 Bus (non-galvanically isolated)
DescriptionECL COMFORT 310/230 V
DHW functionsAnti-bacteria program
Digital inputs type12 V pull-up possible
Display typeLCD dot matrix
EEE category5 small equipment (any external dimension < 50 cm)
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
General functionsAlarm functions
Grade of enclosureIP41
Heat curve setting for heating circuit6 points
In scope of WEEEYes
Number of 3-point motor control outputs3
Number of comfort periods per day3
Number of DHW circuits2
Number of DHW storage tank circuits1
Number of digital inputs4
Number of heating circuits3
Number of pumps5
Number of relay outputs6
Number of Sensor inputs10 pc
Power consumption [W]5 W
REACH Candidate Strip substancesLead (CAS no. 7439-92-1)
Relay output inductive load [A]2 A
Relay output ohmic load [A]4 A
Relay output voltage [V] AC230 V
Sensor cable length [m]200 m
Storage temperature [°C] [Max]70 °C
Storage temperature [°C] [Min]-40 °C
Supply voltage [V] AC230 V
Supply voltage [V] AC [max]244 V
Supply voltage [V] AC [min]207 V
Supply voltage frequency [Hz]50 Hz
Temperature sensors typePt 1000, configurable input
Time switch power backup [h]72 h
Time switch typeWeek
User input typeDisplay