| Product type | Weather compensation system |
| Product group | Heat |
| Supply voltage | 230 V AC |
| Fits with | ECL 210 |
| Leakage class | IP 41 |
| Ambient temperature min | 0 °C |
| Ambient temperature max | 55 °C |
| REACH SVHC substance above 0.1% | Lead |
| Carbon footprint (EPD) | 4.7321 kg CO2e per pcs |
| Country of origin | Denmark |
| Customs tariff code (EU CN) | 90328900 |
| HS code | 9032.89 |
| Manufacturer part number | 087H3020 |
| VVS number | 460944210 |
| EAN | 5710104013206 |
| Net weight | 0.439 Kilogram |
| Type | ECL Comfort 210 |
| Actuator output load [VA] | 15 VA |
| Ambient humidity [% RH] [Max] | 65 % |
| Ambient temperature [°C] [max] | 55 °C |
| Ambient temperature [°C] [min] | 0 °C |
| Application source | By ECL application key |
| Approval | CE |
| Approval standard | EMC-Directive: 2004/108/EC |
| CE mark | Yes |
| China RoHS compliance | Out of scope |
| Communications | ECL 485 Bus (non-galvanically isolated) |
| Description | ECL COMFORT 210/230 V |
| DHW functions | Anti-bacteria program |
| Digital inputs type | 12 V pull-up possible |
| Display type | LCD dot matrix |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| EU RoHS compliance | Yes with exemptions |
| EU RoHS exemption clause | 6(c) |
| General functions | Alarm functions |
| Grade of enclosure | IP41 |
| Heat curve setting for heating circuit | 6 points |
| In scope of WEEE | Yes |
| Number of 3-point motor control outputs | 2 |
| Number of comfort periods per day | 3 |
| Number of DHW circuits | 1 |
| Number of DHW storage tank circuits | 1 |
| Number of digital inputs | 2 |
| Number of heating circuits | 2 |
| Number of pumps | 4 |
| Number of relay outputs | 4 |
| Number of Sensor inputs | 8 pc |
| Power consumption [W] | 5 W |
| REACH Candidate Strip substances | Lead (CAS no. 7439-92-1) |
| Relay output inductive load [A] | 2 A |
| Relay output ohmic load [A] | 4 A |
| Relay output voltage [V] AC | 230 V |
| Sensor cable length [m] | 200 m |
| Sensor cable length [mm] | 200 mm |
| Storage temperature [°C] [Max] | 70 °C |
| Storage temperature [°C] [Min] | -40 °C |
| Supply voltage [V] AC | 230 V |
| Supply voltage [V] AC [max] | 244 V |
| Supply voltage [V] AC [min] | 207 V |
| Supply voltage frequency [Hz] | 50 Hz |
| Temperature sensors type | Pt 1000, configurable input |
| Time switch power backup [h] | 72 h |
| Time switch type | Week |
| User input type | Display |