cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-09
sales@cballast.com
cballast.com

Danfoss CVP-L constant-pressure pilot valve, low pressure -0.66 to 7 bar, for ICS servo-operated main valves (code 027B0920)

Danfoss · HVAC & Refrigeration · Pilot Valves · Denmark · danfoss.com
Part Number
027B0920  ·  HS 8481.80
Danfoss CVP-L constant-pressure pilot valve, low pressure -0.66 to 7 bar, for ICS servo-operated main valves (code 027B0920)

Danfoss CVP-L constant-pressure pilot valve for the ICV Flexline / ICS servo-operated main-valve range, code 027B0920. Fitted in the pilot channel of an ICS main valve, the CVP throttles the pilot flow to hold a constant pressure at the main-valve inlet, independent of the downstream pressure — used for evaporating-pressure and similar constant-pressure duties in industrial refrigeration. This SKU is the low-pressure version with a regulating range of -0.66 to 7 bar (-9.6 to 102 psig). Flow coefficient Kv 0.4 m3/h (Cv 0.46). Maximum working pressure 52 bar (754 psig); media temperature range -60 to 120 C (-76 to 248 F). Zn (TLP) surface coating; supplied as a 6-piece multipack with gasket. For HCFC, HFC, R717 (ammonia) and R744 (CO2) systems.

Technical Specifications

TypeCVP-L (constant-pressure pilot valve)
Code number027B0920
SeriesCVP / CVPP / CVC / CVE / EVM / CVH pilot valves (ICV Flexline)
FunctionConstant-pressure pilot — holds constant inlet pressure
Valve versionLow pressure
Regulating range-0.66 to 7 bar (-9.6 to 102 psig)
Kv value0.4 m3/h
Cv value0.46 gal/min
Maximum working pressure52 bar (754 psig)
Media temperature range-60 to 120 C (-76 to 248 F)
Surface coatingZn (TLP)
Net weight1.365 kg
Gross weight1.608 kg
Packing formatMulti pack (6 pc)
Parts includedGasket
Fluid group1
PED categoryArt. 4, par. 3
BrandICV Flexline
ApprovalsEAC, UL
EAN5702428973236

Properties

MaterialSteel
Pressure rating52 bar
Temperature range-60 to 120 C
MOQ1

Compatibility

Mounts in the pilot channel of Danfoss ICS servo-operated main valves. Select the pilot version by pressure range: CVP-L low (-0.66 to 7 bar, code 027B0920), CVP-M medium (4-28 bar, 027B0921), CVP-H high (25-52 bar, 027B0922). Confirm the ICS valve size and pilot arrangement (single or dual pilot) before ordering.

Approvals

Attached Documents