Danfoss CVH pilot valve body, code 027F1159, steel construction with a NPT 1/4 in connection (13 mm, ANSI/ASME B1.20.1). The CVH is the housing that lets a Danfoss CV-series pilot valve (constant-pressure CVP, differential-pressure CVPP, pressure-operated CVC, electronic CVE or solenoid EVM) operate in an external pilot line rather than being screwed directly into the main-valve top cover. A pilot screwed into a CVH housing can either control small capacities on its own — without a main valve — or act as an external control valve for an ICS, ICF (or discontinued PM) servo-operated main valve. This SKU is the bare CVH housing; the pilot insert and gasket are ordered separately. Maximum working pressure 65 bar (943 psig); media temperature -50 to 120 C (-58 to 248 F); PED Art. 4 par. 3, fluid group 1. For HCFC, HFC, R717 (ammonia) and R744 (CO2) industrial-refrigeration systems. Supplied as multi pack (32 pc).
| Type | CVH (housing for pilot valves, external pilot line) |
| Series | CVP / CVPP / CVC / CVE / EVM pilot valves (ICV Flexline) |
| Function | Receives a CV-series pilot for use in an external pilot line — as an independent small-capacity control valve or as an external control valve for an ICS / ICF main valve |
| Body material | Steel |
| Connection type | NPT |
| Connection size | 1/4 in (13 mm) |
| Connection material | Steel |
| Connection standard | ANSI/ASME B1.20.1 |
| Maximum working pressure | 65 bar (943 psig) |
| Media temperature range | -50 to 120 C (-58 to 248 F) |
| Flow direction indicator | Embossed 1-way arrow |
| Product group | Press. and temp. regul. valves |
| Fluid group | 1 |
| PED category | Art. 4, par. 3 |
| Packing format | Multi pack (32 pc) |
| Net weight | 0.347 kg |
| Gross weight | 0.371 kg |
| REACH candidate substance | contains Lead (CAS 7439-92-1) |
| Approvals | EAC |
| EAN | 5702422107200 |
| MPN | 027F1159 |
| Material | Steel |
| Pressure rating | 65 bar |
| Temperature range | -50 to 120 C |
| Thread standard | ANSI/ASME B1.20.1 |
| MOQ | 1 |
The CVH housing is supplied without a pilot insert. Order the required CV-series pilot separately (CVP constant-pressure, CVPP differential-pressure, CVC pressure-operated, CVE electronic, or EVM solenoid) plus its gasket. Confirm the pilot-line connection type/size and the main-valve arrangement (ICS/ICF) before ordering.