Danfoss CHV-X 100 function module (Top Complete) for industrial refrigeration, code 148B6022. Complete check-valve top part with cone, spring and seat that fits a 100 mm (4 in) SVL Flexline valve housing to build or convert it into a CHV-X 100 check valve. Maximum working pressure 52 bar (754 psig); media temperature range -60 to 150 C (-76 to 302 F). Lets an installed SVL housing be re-functioned or serviced without cutting the body out of the line. For R717 (ammonia), R744 (CO2) and fluorinated refrigerants and their oils.
| Type | CHV-X 100 function module — Top Complete (SVL Flexline) |
| Code number | 148B6022 |
| Series | CHV-X |
| Function | Check valve top part (cone + spring + seat) |
| Fits | 100 mm (4 in) SVL Flexline valve housing |
| Maximum working pressure | 52 bar (754 psig) |
| Media temperature range | -60 to 150 C (-76 to 302 F) |
| Applicable media | R717 (ammonia), R744 (CO2), HCFC/HFC refrigerants and oils |
| Approvals | CE |
| EAN | 5702428486262 |
| Brand | SVL Flexline |
| Product group | Check valves |
| Type designation | Top Complete |
| Max. working pressure | 52.0 bar |
| Temperature range | -60 °C to 150 °C |
| Refrigerants | R1234yf; R1234ze(E); R125; R134a; R152a; R170; R22; R227ea; R236fa; R245fa; R290; R32; R401A; R402A; R404A; R407A; R407B; R407C; R407F; R407H; R409A; R410A; R413A; R417A; R421A; R422A; R422B; R422D; R438A; R442A; R444B; R447A; R447B; R448A; R449A; R449B; R450A; R452A; R452B; R452C; R454A; R454B; R454C; R455A; R463A; R502; R507A; R512A; R513A; R513B; R515A; R515B; R516A; R600; R600a; R717; R744 |
| REACH candidate-list substances | No |
| Net weight | 5.552 kg |
| EU RoHS compliance | Yes |
| Approval | CE |
| China RoHS compliance | Yes |
| Max. Working Pressure [bar] | 52 bar |
| Max. Working Pressure [psig] | 754 psig |
| Temperature range [°C] [max] | 150 °C |
| Temperature range [°C] [min] | -60 °C |
| Temperature range [°F] [max] | 302 °F |
| Temperature range [°F] [min] | -76 °F |
| Used for product | CHV-X 100 |
| Material | Steel |
| Pressure rating | 52 bar |
| Temperature range | -60 to 150 C |
| Standard size | 100 mm |
| MOQ | 1 |
Danfoss SVL Flexline CHV-X 100 function module (Top Complete). Fits the 100 mm SVL valve bodies 148B6014 (angleway EN), 148B6015 (straightway EN), 148B6016/148B6017 (ASME). The complete CHV-X 100 check valves are codes 148B6036 (EN) and 148B6037 (ASME). Function module is HS 8481.90 (valve part).