Danfoss AXV 11H2 hot gas bypass controller (code 034L0010) for R134a refrigeration systems. The AXV opens on falling evaporating pressure and injects hot gas from the discharge line to maintain a minimum evaporating pressure at low load, providing modulating capacity control and stable low-load operation. This SKU has 3/8 in ODF solder connections, a regulating range of 0.5 – 3.2 bar (factory set at 2.5 bar) and a maximum working pressure of 49 bar (711 psig). UL listed (C UL US). Price on quote.
| Type | Hot gas bypass controller |
| AXV 11H2 Code number | 034L0010 Series: Danfoss AXV hot gas bypass controller Function: Hot-gas bypass / capacity regulation, modulating Connection: 3/8 in ODF solder, inlet and outlet Connection type: Solder |
| ODF Regulating range | 0.5 – 3.2 bar (factory setting 2.5 bar) Max. working pressure (PB/MWP): 49 bar (711 psig) Refrigerant: R134a Conformity assessment: PED category Art. 4, par. 3 (sound engineering practice) Approvals: UL (C UL US Listed) Net weight: 0.180 kg Gross weight: 0.211 kg EAN: 5715255248217 Product group: Press. and temp. regul. valves Approval: C UL US LISTED Body material: Stainless steel Connection material: Bi-metal: Steel/copper Direction: Angleway Factory setting [bar]: 2.5 bar Factory setting [psig]: 36.1 psig Flow direction: Single-flow Flow direction indicator: Laser engraved 1-way arrow Fluid Group: 2 Inlet connection type: Solder, ODF Inlet size [in]: 3/8 in Max. Working Pressure [bar]: 49 bar Max. Working Pressure [psig]: 711 psig Orifice capacities [kW]: 3.64 kW Orifice capacities [TR]: 1.04 TR Orifice size: 11 Outlet connection type: Solder, ODF Outlet size [in]: 3/8 in PED category: Art. 4, par. 3 Pressure equalization: Internally equalized Pressure range [bar] [max]: 3.2 bar Pressure range [bar] [min]: 0.5 bar Pressure range [psi] [max]: 46 psi Pressure range [psi] [min]: 7 psi Refrigerants: R134a Spring type: 2 UL approved refrigerants: R134a |
| Material | Steel body; copper ODF connection stubs |
| Pressure rating | 49 bar (711 psig) |
| Primary standard | Danfoss AXV |
| Standard size | 3/8 in |
| MOQ | 1 |
Danfoss AXV hot gas bypass regulator for R134a systems. A liquid injection line (thermostatic expansion valve) is normally required for de-superheating with hot-gas bypass. Confirm the 3/8 in ODF solder connection and R134a application before ordering.