cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss AVQM-WE motorized flow controller (PICV), PN 25, DN 50, flow range 0.8–14 m³/h, Kvs 25 m³/h, Flange DN 50 (EN 1092-2) (003H7090)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003H7090  ·  HS 8481.80
Danfoss AVQM-WE motorized flow controller (PICV), PN 25, DN 50, flow range 0.8–14 m³/h, Kvs 25 m³/h, Flange DN 50 (EN 1092-2) (003H7090)

Danfoss AVQM-WE (003H7090) — self-acting flow controller with integrated, pressure-independent motorized control valve (PICV); holds the differential pressure across the built-in flow restrictor constant so the electric actuator stem position sets flow independent of system pressure; limits the flow to the set maximum, PN 25, DN 50, for district heating and cooling systems. Because the built-in differential-pressure controller keeps the pressure drop across the flow restrictor constant, the flow becomes pressure-independent: the position of the separately ordered Danfoss AMV(E) electric actuator directly sets the flow, and the valve limits the flow to the set maximum. Flow range 0.8 - 14 m³/h; Kvs 25 m³/h; flow-restrictor differential pressure (Δpb) 0.2 bar; maximum differential pressure 16 bar; media temperature 2–150 °C; seat leakage 0.05 % Kvs (IEC 60534). Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); stainless-steel seat/cone; EPDM control diaphragm. Connection Flange DN 50 (EN 1092-2). Mounting version Free. Permissible media: district-heating/cooling circulation water (glycolic water up to 30 %), pH 7–10. The controller is delivered completely assembled, including the impulse tube between valve and actuator; the AMV(E) electric actuator are ordered separately. OEM P/N 003H7090. Materials and function per Danfoss AVQM-WE / AVQMT-WE (new neck) data sheet; technical values verbatim from store.danfoss.com (code 003H7090). Contains lead per the REACH candidate list. differential pressure 16 bar); Temperature range: 2 to 150 °C (district heating/cooling water); Standards: EN 1092-2, IEC 60534; HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.

Technical Specifications

Code number003H7090
TypeAVQM-WE
Product groupPressure independent control valves (Pressure and flow controllers)
FunctionSelf-acting flow controller with integrated, pressure-independent motorized control valve (PICV); holds the differential pressure across the built-in flow restrictor constant so the electric actuator stem position sets flow independent of system pressure; limits the flow to the set maximum
Valve sizeDN 50
Pressure classPN 25
ConnectionFlange DN 50 (EN 1092-2)
Kvs value25 m³/h
Flow rate range0.8 - 14 m³/h
Flow restrictor differential pressure (Δpb)0.2 bar
Max. differential pressure16 bar
Media temperature2 - 150 °C
MediaDistrict heating / district cooling circulation water (glycolic water up to 30%), pH 7 - 10
Seat leakage rate0.05 % Kvs (IEC 60534)
Electric actuatorDanfoss AMV(E) (e.g. AMV/AME 110, 150, 435), ordered separately; controllable by ECL electronic controllers
DeliveryDelivered assembled, incl. impulse tube between valve and actuator; electric actuator ordered separately
Mounting versionFree
Valve body materialDuctile iron EN-GJS-400-18-LT (GGG 40.3)
Valve seat / coneStainless steel
Control diaphragmEPDM
EU RoHS complianceYes with exemptions (6(c))
REACH Candidate List substanceLead (CAS no. 7439-92-1)
China RoHSOut of scope
Net weight13.82 kg
Gross weight13.82 kg
EAN5710104094014

Properties

MaterialValve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve seat/cone Stainless steel; control diaphragm EPDM
Pressure ratingPN 25 (max. differential pressure 16 bar)
Temperature range2 to 150 °C (district heating/cooling water)
MOQ1

Compatibility

Danfoss AVQM-WE for DN 50 district-heating/cooling combined flow limiting and pressure-independent flow control at PN 25. Set the maximum flow within 0.8 - 14 m³/h using the adjustable flow restrictor (Kvs 25 m³/h); because control is pressure-independent, the flow follows the electric actuator position regardless of Δp swings (up to 16 bar). Fit a Danfoss AMV(E) electric actuator (ordered separately), controllable by an ECL electronic controller. Confirm the connection (Flange DN 50 (EN 1092-2)) and pressure class (PN 25) match the pipework; order the matching flange set separately. Media temperature up to 150 °C.

Standards

Attached Documents