Danfoss AVQM flow controller with integrated control valve (PICV), PN 25, DN 32, flow range 0.4–10 m³/h, Kvs 12.5 m³/h, Flange DN 32 (003H6756)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003H6756  ·  HS 8481.80
Danfoss AVQM flow controller with integrated control valve (PICV), PN 25, DN 32, flow range 0.4–10 m³/h, Kvs 12.5 m³/h, Flange DN 32 (003H6756)

Danfoss AVQM (003H6756) — self-acting flow controller with integrated control valve, PN 25, DN 32, for district heating and cooling systems. The AVQM holds the flow rate constant and limits it to the set maximum; the integrated control valve accepts a Danfoss AMV(E) electric actuator for combined flow and temperature control. It comprises a control valve with adjustable flow limiter, a connection neck for the electric actuator and a pressure actuator with one control diaphragm. Flow range 0.4–10 m³/h; flow-restrictor differential pressure 0.2 bar; Kvs 12.5 m³/h. Maximum differential-pressure range 16 bar; media temperature 2–150 °C; cavitation factor z ≥ 0.6; seat leakage 0.05 % Kvs (IEC 60534). Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; seat Stainless steel, mat. 1.4571; control diaphragm EPDM. Connection Flange DN 32 (EN 1092-2). Mounting version Free. Permissible media: District heating/cooling circulation water (Glycolic water up to 30%), pH 7–10. OEM P/N 003H6756. Technical data quoted verbatim from store.danfoss.com (code 003H6756) and the Danfoss AVQM (PN 25) data sheet. 1.4571; control diaphragm EPDM; Pressure rating: PN 25 (max. differential-pressure range 16 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.

Technical Specifications

Code number003H6756
TypeAVQM
Product groupPressure and flow controllers
FunctionSelf-acting flow controller with integrated control valve (limits max. flow; accepts AMV(E) actuator)
Valve sizeDN 32
Pressure classPN 25
ConnectionFlange DN 32 (EN 1092-2)
Kvs value12.5 m³/h
Flow rate range0.4 - 10 m³/h
Flow restrictor differential pressure (Δpb)0.2 bar
Max. differential pressure range16 bar
Media temperature2 - 150 °C
Media pH7 - 10
Cavitation factor z≥ 0.6
Seat leakage rate0.05 % Kvs (IEC 60534)
Mounting versionFree
Stem positionNormally open
Stroke10 mm
Permissible mediaDistrict heating/cooling circulation water (Glycolic water up to 30%)
Valve body materialDuctile iron EN-GJS-400-18-LT (GGG 40.3)
Valve cone materialDezincing free brass CuZn36Pb2As
Valve seat materialStainless steel, mat. No. 1.4571
Actuator diaphragmEPDM
EU RoHS complianceYes with exemptions (6(c))
REACH Candidate List substanceLead (CAS no. 7439-92-1)
China RoHSOut of scope
Net weight9.452 kg
Gross weight10.09 kg
EAN5702421542774

Properties

MaterialValve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; valve seat Stainless steel, mat. No. 1.4571; control diaphragm EPDM
Pressure ratingPN 25 (max. differential-pressure range 16 bar)
Temperature range2 to 150 °C (district heating/cooling water)
MOQ1

Compatibility

Danfoss AVQM for DN 32 district-heating/cooling flow (PICV) control at PN 25. Set the maximum flow within 0.4–10 m³/h using the adjustable flow restrictor (Kvs 12.5 m³/h). The integrated control valve accepts a Danfoss AMV(E) actuator for combined flow/temperature control (ordered separately). Confirm the connection (Flange DN 32 (EN 1092-2)) and pressure class (PN 25) match the pipework; order the matching counter-flange/gasket set separately. Maximum differential-pressure range 16 bar, media temperature up to 150 °C.