Danfoss AVQM (003H6756) — self-acting flow controller with integrated control valve, PN 25, DN 32, for district heating and cooling systems. The AVQM holds the flow rate constant and limits it to the set maximum; the integrated control valve accepts a Danfoss AMV(E) electric actuator for combined flow and temperature control. It comprises a control valve with adjustable flow limiter, a connection neck for the electric actuator and a pressure actuator with one control diaphragm. Flow range 0.4–10 m³/h; flow-restrictor differential pressure 0.2 bar; Kvs 12.5 m³/h. Maximum differential-pressure range 16 bar; media temperature 2–150 °C; cavitation factor z ≥ 0.6; seat leakage 0.05 % Kvs (IEC 60534). Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; seat Stainless steel, mat. 1.4571; control diaphragm EPDM. Connection Flange DN 32 (EN 1092-2). Mounting version Free. Permissible media: District heating/cooling circulation water (Glycolic water up to 30%), pH 7–10. OEM P/N 003H6756. Technical data quoted verbatim from store.danfoss.com (code 003H6756) and the Danfoss AVQM (PN 25) data sheet. 1.4571; control diaphragm EPDM; Pressure rating: PN 25 (max. differential-pressure range 16 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
| Code number | 003H6756 |
| Type | AVQM |
| Product group | Pressure and flow controllers |
| Function | Self-acting flow controller with integrated control valve (limits max. flow; accepts AMV(E) actuator) |
| Valve size | DN 32 |
| Pressure class | PN 25 |
| Connection | Flange DN 32 (EN 1092-2) |
| Kvs value | 12.5 m³/h |
| Flow rate range | 0.4 - 10 m³/h |
| Flow restrictor differential pressure (Δpb) | 0.2 bar |
| Max. differential pressure range | 16 bar |
| Media temperature | 2 - 150 °C |
| Media pH | 7 - 10 |
| Cavitation factor z | ≥ 0.6 |
| Seat leakage rate | 0.05 % Kvs (IEC 60534) |
| Mounting version | Free |
| Stem position | Normally open |
| Stroke | 10 mm |
| Permissible media | District heating/cooling circulation water (Glycolic water up to 30%) |
| Valve body material | Ductile iron EN-GJS-400-18-LT (GGG 40.3) |
| Valve cone material | Dezincing free brass CuZn36Pb2As |
| Valve seat material | Stainless steel, mat. No. 1.4571 |
| Actuator diaphragm | EPDM |
| EU RoHS compliance | Yes with exemptions (6(c)) |
| REACH Candidate List substance | Lead (CAS no. 7439-92-1) |
| China RoHS | Out of scope |
| Net weight | 9.452 kg |
| Gross weight | 10.09 kg |
| EAN | 5702421542774 |
| Material | Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; valve seat Stainless steel, mat. No. 1.4571; control diaphragm EPDM |
| Pressure rating | PN 25 (max. differential-pressure range 16 bar) |
| Temperature range | 2 to 150 °C (district heating/cooling water) |
| MOQ | 1 |
Danfoss AVQM for DN 32 district-heating/cooling flow (PICV) control at PN 25. Set the maximum flow within 0.4–10 m³/h using the adjustable flow restrictor (Kvs 12.5 m³/h). The integrated control valve accepts a Danfoss AMV(E) actuator for combined flow/temperature control (ordered separately). Confirm the connection (Flange DN 32 (EN 1092-2)) and pressure class (PN 25) match the pipework; order the matching counter-flange/gasket set separately. Maximum differential-pressure range 16 bar, media temperature up to 150 °C.