Danfoss ASV-PV 3G DN 50 — third-generation self-acting differential-pressure controller for automatic hydronic balancing. Installed in the return pipe of a heating or cooling circuit, it holds a constant differential pressure across the branch or terminal (paired with an ASV-BD/ASV-M/ASV-I partner valve and an impulse tube), so that two-way control-valve authority stays high and flow noise is avoided at part load. Differential-pressure setting range 20-40 kPa (factory setting ), Kvs 20 m³/h, body, Flange connection,, media temperature to, integral shut-off. OEM P/N 003Z0626. EAN 5710104523910. Technical data quoted verbatim from store.danfoss.com (code 003Z0626).
| Code number | 003Z0626 |
| Type | ASV-PV 3G |
| Product group | Automatic balancing |
| Description | ASV-PV 3G, DN 50, 20-40 kPa, automatic balancing valve |
| Valve size | DN 50 |
| Connection types | Flange |
| Kvs values [m³/h] | 20 m³/h |
| Differential pressure setting [kPa] [Min] | 20 KPa |
| Differential pressure setting [kPa] [Max] | 40 KPa |
| Contains batteries | No |
| EU RoHS compliance | Out of scope |
| China RoHS compliance | Out of scope |
| Net weight | 6.375 Kilogram |
| Gross weight | 7.232 Kilogram |
| Volume | 18.546 Liter |
| EAN | 5710104523910 |
| MOQ | 1 |
Danfoss ASV-PV 3G differential-pressure controller for DN 50 circuits. The valve maintains a set differential pressure and is used with a matching ASV-BD/ASV-M/ASV-I partner (manual balancing / shut-off) valve; select the setting range (20-40 kPa here) to bracket the required branch differential pressure, and confirm the connection type (Flange) matches the pipework. Impulse tube is supplied with the valve.