Danfoss MBS 3350 pressure transmitter, genuine OEM code 060G6657. Measuring range 0 to 10 bar (0 to 145 psi), 4-20 mA (2-wire) output, AISI 316L stainless steel wetted parts. Flange, Port Ø2.5 pressure connection; Cable. Reference gauge (relative), enclosure IP67. ATEX Ex ec IIA T4 Gc; CE; UL Recognized; C UL US.; EAN 5702428005661.
| Type | MBS 3350 |
| Range | 0 to 10 bar (0 to 145 psi) |
| Reference | gauge (relative) |
| Output | 4-20 mA (2-wire) |
| Supply | 9-32 V DC |
| Wetted parts | AISI 316L stainless steel |
| Pressure connection | Flange, Port Ø2.5 |
| Electrical connection | Cable |
| Enclosure | IP67 |
| Accuracy | 0.5% FS typical, 1% FS max |
| Approvals | ATEX Ex ec IIA T4 Gc; CE; UL Recognized; C UL US |
| EAN | 5702428005661 |
| Part number | 060G6657 |
| Net weight | 0.349 Kilogram |
| Product group | Sensors |
| + supply | Black |
| - supply | Blue |
| Accuracy, max. [±FS%] | 1 % |
| Accuracy, typical [±FS%] | 0.5 % |
| Ambient temperature range [°C] [max] | 100 °C |
| Ambient temperature range [°C] [min] | -30 °C |
| Ambient temperature range [°F] [max] | 212 °F |
| Ambient temperature range [°F] [min] | -22 °F |
| Approval | ATEX |
| Approval comments | ATEX Ex ec IIA T4 Gc |
| Cable length [in] | 21.65 in |
| Cable length [m] | 0.55 m |
| CE mark | Yes |
| China RoHS compliance | Out of scope |
| Comments | SCREEN: CONNECTED TO ENCLOSURE |
| Compensated temp. range [°C] [max] | 100 °C |
| Compensated temp. range [°C] [min] | 0 °C |
| Compensated temp. range [°F] [max] | 212 °F |
| Compensated temp. range [°F] [min] | 32 °F |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| Electrical conn. comments | Screened Ship |
| Enclosure rating IP | IP67 |
| EU RoHS compliance | Yes with exemptions |
| EU RoHS exemption clause | 6(c) |
| Flush diaphragm | No |
| High Clipping Level | 22.4 |
| In scope of WEEE | Yes |
| International Article Number | 5702428005661 |
| Intrinsically safe | No |
| Low Clipping level | 3.6 |
| Medium temperature range [°C] [max] | 125 °C |
| Medium temperature range [°C] [min] | -20 °C |
| Medium temperature range [°F] [max] | 257 °F |
| Medium temperature range [°F] [min] | -4 °F |
| Non-linearity BFSL [±FS%] | 0.2 % |
| Output signal | Current |
| Output signal [mA] [max] | 20 mA |
| Output signal [mA] [min] | 4 mA |
| Overload pressure max. [bar] | 60 bar |
| Overload pressure max. [psi] | 870 psi |
| Pressure connection notes | Block adapter with flange |
| Pressure connection size | Port Ø2.5 |
| Pressure connection standard | N/A |
| Pressure connection type | Flange |
| Pressure Male/Female | Female |
| Pressure range [bar] [max] | 10 bar |
| Pressure range [bar] [min] | 0 bar |
| Pressure range [psi] [max] | 145 psi |
| Pressure range [psi] [min] | 0 psi |
| Pressure reference | Gauge (relative) |
| Pulse-snubber | Yes |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Response time max. [ms] | 4 ms |
| Specification key | MBS 3350-2011-DDCD28-3 |
| Supply voltage [V] DC [max] | 32 V |
| Supply voltage [V] DC [min] | 9 V |
| UL mark | Yes |
| Material | AISI 316L stainless steel wetted parts |
| Pressure rating | 0 to 10 bar (0 to 145 psi) |
| Temperature range | -40 to +125 C (medium) |
| IP rating | IP67 |
| Thread standard | Flange, Port Ø2.5 |
| MOQ | 1 |
MBS 3350 0-10 bar gauge, Ø2.5 flush flange with cable outlet.