Danfoss 060-110191 KP1 pressure switch. Danfoss OEM. Danfoss pressure sensors for industrial and marine service. Standard 4-20mA output.
| Approval | CE, EAC, UL, ATEX II 1G Ex ia IIC T4 Ga (Ex models), IECEx, DNV, LR |
| Standards | IECEx, IEC 61298-2 |
| Approvals | DNV, LR, CE |
| HS code | 9031.80 |
| Code number | 060-110191 |
| Product type | KP1 |
| Product group | Switches and thermostats |
| Max. test pressure | 290.0 psig |
| Max. test pressure Pe | 20.0 bar |
| Max. working pressure | 17.0 bar |
| Ambient temperature range | -25 °C to 65 °C |
| Refrigerants | R113; R1233zd(E); R1234yf; R1234yz; R1234ze(E); R124; R134a; R22; R404A; R407A; R407C; R407F; R407H; R422B; R422D; R438A; R448A; R449A; R449B; R450A; R452A; R454C; R455A; R507A; R513A; R515B |
| Lubricants compatibility | Oilfree applications |
| Fluid Group | 1 |
| PED category | IV |
| UL approval file name | E31024; MH27572 |
| UL approved refrigerants | R113; R124; R134a; R22; R404A; R407A; R407C; R407F; R407H; R422B; R422D; R438A; R448A; R449A; R449B; R450A; R452A; R507A; R513A; R515B |
| UL mark | Yes |
| CE mark | Yes |
| REACH candidate-list substances | Lead (CAS no. 7439-92-1); Cadmium oxide (CAS no.1306-19-0) |
| Net weight | 0.3 kg |
| EAN | 5702424497736 |
| Amb | |
| Temp | |
| Note | 80 °C/176 °F for max 120 min |
| Application note | Not applicable for liquid line |
| Contact function | SPDT |
| Contact rating | AC15=10 A, 400 V; AC1=16 A, 400 V; AC3=16 A, 400 V; DC13=12 W, 220 V; LR=112 A, 400 V |
| Differential | 0.70 bar to 4.00 bar |
| Electrical connection | Rubber cable gland |
| Electrical connection size | 6-14 mm |
| EN 60947 electrical properties | Insulation: 400V; Pollution degree: 3; Rated impulse voltage: 4 kV; Short circuit prot, fuse: 16A |
| EN 60947 wiring properties | Flex, ferrules: 0.5-1.5 mm2; Flex, no ferrules: 0.7-2.5 mm2; Solid/stranded: 0.75-2.5 mm2 |
| Enclosure rating IP | IP44 |
| Enclosure rating Nema (~) | 2 |
| Oil free refrigerants | R134a; R513A; R515B |
| Other RoHS documentation | Saudi Arabia RoHS |
| Pressure connection size | 1/4 |
| Pressure connection standard | DIN 8906 |
| Pressure connection type | Flare |
| Pressure Male/Female | Male |
| Pressure sensing element | Bellows |
| MOQ | 1 |
Standard 4-20mA output. Check pressure/temperature range and thread.